WAYNE COMBUSTION SYSTEMS

801 GLASGOW AVE.

FORT WAYNE, IN 46803

ELECTRIC SHOCK HAZARD

OVERHEATING HAZARD

HIGH VOLTAGES ARE PRESENT IN THIS EQUIPMENT.
FOLLOW THESE RULES TO AVOID ELECTRIC SHOCK.

s

Use only a properly grounded circuit. A ground fault
interrupter is recommended.

s

Do not spray water directly on burner.

s

Turn off power before servicing.

s

Read the owner’s manual before using.

SHOULD OVERHEATING OCCUR:

s

Shut off the manual gas valve to the appliance.

s

Do not shut off the control switch to the pump or blower.

SPECIFICATIONS

FOR YOUR SAFETY

IF YOU SMELL GAS:

1.  OPEN WINDOWS
2.  DON’T TOUCH ELECTRICAL SWITCHES
3.  EXTINGUISH ANY OPEN FLAME
4.  IMMEDIATELY CALL YOUR GAS

SUPPLIER.

THESE INSTRUCTIONS SHOULD BE
AFFIXED TO THE BURNER OR
ADJACENT TO THE HEATING
APPLIANCE.

FOR SHIPPING PURPOSES, THE FLAME
SPREADER IS FULLY RETRACTED.  
FLAME SPREADER ADJUSTMENT IS
MANDATORY AND EFFECTS BURNER
IGNITION AND PERFORMANCE.

MODELS

P250AF

P265

P265EP

P250AFEP

P265F

P265DI

P250AFDI

P265FEP

GAS BURNER

Publication Date 5/01   -   Revision B   -   Manual 101220

NOTE:  Dimensions in (  ) are informational only.  English values take priority.

WARNING: If the information in these
instructions is not followed exactly, a fire or
explosion may result causing property
damage, personal injury or death.

-

Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.

-

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any

phone in your building.

• Immediately call your gas supplier from a neighbor’s

phone.  Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier, call the fire

department.

-

Installation and service must be performed by a qualified
installer, service agency or the gas supplier.

CARBON MONOXIDE IS A COLORLESS, ODORLESS GAS
THAT CAN KILL. FOLLOW THESE RULES TO CONTROL
CARBON MONOXIDE.

s

Do not use this burner if in an unvented, enclosed area. Carbon
monoxide may accumulate.

s

Do not adjust the pressure regulator. High pressures produce
carbon monoxide.

s

Check flue gases for carbon monoxide. This check requires
specialized equipment.

s

Allow only qualified burner service persons to adjust the burner.

Special instruments and training are required.

s

Read the owner’s manual before using.

CARBON MONOXIDE

POISONING HAZARD

NOTICE

BURNER MODELS

MINIMUM INPUT

MAXIMUM INPUT

FUELS

P250AF & P250AF-EP & P250AFDI

50,000 BTU/Hr (14.65 kW/Hr)

250,000 BTU/Hr (73.27 kW/Hr)

Natural & L.P. Gas

P265 & P265EP

65,000 BTU/Hr (19.05 kW/Hr)

200,000 BTU/Hr (58.61 kW/Hr)

Natural & L.P. Gas

P265F & P265FEP

65,000 BTU/Hr (19.05 kW/Hr)

200,000 BTU/Hr (58.61 kW/Hr)

Natural & L.P. Gas

ELECTRICAL Power Supply - 115V/60HZ 1 Ph.

MOUNTING:  Adjustable Flange is Standard

Pedestal Mount is Optional.

Summary of Contents for P265DI

Page 1: ...store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical sw...

Page 2: ...have been heated adequately without wide variations in temperature without objectionable drafts and without excessive fuel costs in the past If the heating system is deficient with respect to any of t...

Page 3: ...plugs or any other condition which might make the unit unsatisfactory for gas conversion is found proper arrangements should be made for replacement or repair before proceeding with the burner install...

Page 4: ...ssure point adjuster Insert in slot cut in flue pipe When adjustment is completed scribe a line on adjuster so it can be relocated Remove adjuster trim off excess slit remainder vertically and bend se...

Page 5: ...152 4mm 180 000 52 75 250 000 73 27 7 inch 177 8mm NOTE If the flue pipe exceeds 10 ft 3 048m in length or contains more than two elbows use next size larger pipe and draft hood NO MOVEABLE FLUE PIPE...

Page 6: ...er was designed especially for converting gun fired oil designed furnaces and boilers Due consideration was given to making it as simple easy to install and service as possible without weakening its d...

Page 7: ...00 29 31 64 41290 8 203 2 X 8 203 2 plus back up of plus 1 1 2 38 1mm 120 000 35 17 72 1 4 46610 8 1 2 215 9 x 8 1 2 215 9 1 1 2 38 1mm magnesia 140 000 41 03 81 52260 9 228 6 x 9 228 6 or more loose...

Page 8: ...ll piping must comply with local codes and ordinances or the National Fuel Gas Code ANSI Z223 1 1984 and NFPA No 54 A sediment trap or drip leg must be installed in the supply line to the burner A uni...

Page 9: ...8 9 525 3 8 9 525 9 16 14 29 1 2 12 7 1 2 12 7 3 4 19 05 3 4 19 05 1 2 9 16 14 29 13 16 20 64 1 25 4 9 16 14 29 1 25 4 PIPE CAPACITY TABLE Nominal Diameter of Pipe in Inches mm 3 4 19 05 1 25 4 1 1 4...

Page 10: ...it snaps Repeat this until the pilot lights Note this may take some time until all the air is bled out of the line 7 Hold the red button on the valve for 60 seconds then release 8 Observe pilot if not...

Page 11: ...10 P265DI JUNCTION BOX ROTATED JUNCTION BOX NOT ROTATED COMBINATION GAS VALVE P265DI...

Page 12: ...primary air both of which could be caused by over firing The only answer is to reduce the firing rate or increase the primary air Combustion efficiency is determined by the percent CO2 and the tempera...

Page 13: ...liquids The flow of combustion and ventilating air to the burner must not be blocked or obstructed in any manner CLEANING OF BURNERS Remove the burner from the appliance and visually inspect the blas...

Page 14: ...the flame current also holds the safety lockout timer in the reset or normal operating condition SAFETY LOCKOUT TIME S8600 only The safety lockout timer circuit starts timing the moment the trial for...

Page 15: ...t burner lights Module senses flame current OR Pilot burner does not light Module Response S8600A F Ignition spark continues pilot valve remains S8610A F open until system is reset S8600B H After 15 o...

Page 16: ...that pilot flame covers flame rod and is steady and blue Adjust pilot flame If problem persists replace the module NOTE If S8600B H S8610B H goes into lockout reset system For S8600M wait 6 min nom f...

Page 17: ...On a call for heat voltage is applied to the ignitor across Terminals 1 power and 6 ground of the input connector A high voltage spark is then generated from the spark electrode to ground Simultaneous...

Page 18: ...ILABLE AND YOU ARE A CERTIFIED INSTALLER I VOLT METER VOLTS OHMS CONTINUITY 2 AMP METER CLAMP TYPE 3 BURNER MANUAL 4 MANOMETER 5 BLADE SCREW DRIVERS 6 NUT DRIVERS 7 OPEN END WRENCHS 8 TAPE MEASURE The...

Page 19: ...volts are present on the coil side but we do not have 115 volts on the contact side of the relay then check the voltage supply or look for a blown fuse The 115 volts are supplied from LI Hot and L2 N...

Page 20: ...on junction box have shorted to the junction box E Bad Thermostat F Blower wheel Jammed G Excessive amount of debris stuck in blower wheel blades H 24 volt transformer is not functioning properly I T...

Page 21: ...20 WIRING TROUBLESHOOTING DIAGRAM HONEYWELL S87KDI OPERATING SYSTEM...

Page 22: ...or should be relocated to an area that is within this temperature range 8 Relative Humidity The S87K is coated for moisture resistance from 5 95 relative humidity at 90 F 32 C Caution should be taken...

Page 23: ...t Spark DI 1 62898 001 Orifice Holder 5 127mm Units 1 60249 Orifice Holder 8 203 2mm Units 1 60250 Orifice Holder 11 279 4mm Units 1 See Chart Orifices Natural gas 1 See Chart Orifices LP gas 1 61455...

Page 24: ...1 See Chart Orifices Natural gas 1 See Chart Orifices LP gas 1 60680 002 Pilot Orifice Natural gas 1 60680 Pilot Orifice LP gas 1 60987 Thermocouple 1 61818 Flamespreader 1 63213 001 Piezo Spark Gener...

Page 25: ...his LIMITED WARRANTY by WAYNE shall be repaired or replaced at WAYNE s sole option 3 WAYNE is not responsible for any labor cost for the removal and replacement of said burner or burner components and...

Page 26: ...25 Notes...