IR
–Decoder
Parameter
Parameter
Setting
Use pair F for
set programming mode (Left: Off / Right: On)
IR-Channel F
This parameter determines which mode pair F is used.
IR-Channel F
: Configuration of button pair F possible
Programming Mode
: Pair F is used only for enable or disable programming mode via IR remote control.
Value of IR-locking object after bus voltage recovery
Off (0)
On (1)
as before bus voltage failure
query via bus
This parameter determines which value the locking object for the IR decoder will take when bus voltage returns.
Detect long key press for dimming, shutter and
stepping after
0.5 seconds
; 0.6 seconds; 0.8 seconds; 1.0 seconds; 1.2
second; 1.5 seconds; 2.0 seconds; 2.5 seconds; 3.0
seconds; 4.0 seconds; 5.0 seconds; 6.0 seconds; 7.0
seconds; 10.0 seconds
This parameter determines the time from which holding down a key for the dimming, shutter or dimming with value is
deemed a long key press.
Detect long key press for scene saving after
0.5 seconds
; 0.6 seconds; 0.8 seconds; 1.0 seconds; 1.2
second; 1.5 seconds; 2.0 seconds; 2.5 seconds; 3.0
seconds; 4.0 seconds; 5.0 seconds; 6.0 seconds; 7.0
seconds; 10.0 seconds
This parameter determines the time from which holding down a key for the scene saving function is deemed a long key
press.
66
Output dimming value Slave2 (continuous)
dimming value
1 Byte
5.001
CWT
Via this object the controller sends the dimming values for the second additional lighting group.
67
Output switching Slave3 (continuous)
On/Off
1 bit
1.001
CWT
Via this object the controller sends on and off control commands to the third additional lighting group. It sends the value
“On” when the brightness is below the defined brightness setpoint for a defined time. It sends the value “Off” when the
controller received a logical
“0” via object 53 or when the controller changes from the state “active” to the state
“standby”.
68
Output dimming value Slave3 (continuous)
dimming value
1 Byte
5.001
CWT
Via this object the controller sends the dimming values for the third additional lighting group.
69
Output switching Slave4 (continuous)
On/Off
1 bit
1.001
CWT
Via this object the controller sends on and off control commands to the fourth additional lighting group. It sends the
value “On” when the brightness is below the defined brightness setpoint for a defined time. It sends the value “Off” when
the controller received a logical
“0” via object 53 or when the controller changes from the state “active” to the state
“standby”.
70
Output dimming value Slave4 (continuous)
dimming value
1 Byte
5.001
CWT
Via this object the controller sends the dimming values for the fourth additional lighting group.
71
Calibration of master (continuous)
1=Start / 0=Stop
1 bit
1.010
CWT
Via this object the calibration process of the controller is started with a logical “1”.
Required is that controller has status „inactive“.
After completion of the calibration process the controller is in the state “inactive”.
Via
this object the calibration process of the controller is stopped with a logical “0”.
Note: After a successful calibration the actuators are dimmed to 50%. After a failed calibration the actuators are dimmed