Switch-Off
Parameter
Setting
Switch off, if brightness is higher than xx LUX
250 - 1600
, 900
This parameter determines the starting brightness value from which the “Switching off” telegram (object no. 52) will be sent.
Note 1: The internal light sensor has a measurement range from 20 to 1000 LUX. It is therefore sensible to set a threshold above 1000
LUX only if an external sensor, having a corresponding measurement range, is used for brightness measurement, or indirect
measurement has been configured.
Note 2: Depending on the internal recalculation of the value, this can cause impreciseness when resolving of approximately 5%.
Switch off, not before xx seconds.
0 -59,
20
This parameter determines the interval at which the corresponding telegram for switching off is sent after exceeding the nominal
brightness value.
Communication objects
Obj.-no.
Object name
Function
Type
Flags
44
Control unit On/Off (on-off)
On/Off
1 bit
1.001
CWT
This object switches the controller on or off per group address. This information can come from a bus button or from the output object
of a presence detector, for example.
45
Automatic mode (on-off)
On/Off
1 bit
CWT
The controller notifies its internal status to the outside world via this object. The status can either have
the value “On,” i.e. the controller
works in automatic mode, or the value “Off.” Moreover, this does not differentiate between whether the controller was switched off
manually or by override.
Describing this object has no effect.
46
Setpoint for switching on
value in LUX
2 Byte
9.004
CRW
This object notifies the brightness controller of the setpoint for switching on in automatic mode. Until the first occurrence of a value,
the value from the parameter “Switch on if brightness value less than xx LUX” is used as the setpoint.
This object is saved at bus voltage failure and restored at bus voltage recovery.
47
Setpoint for switching off
value in LUX
2 Byte
9.004
CRW
This object notifies the brightness controller of the setpoint for switching off in automatic mode. Until the first occurrence of a value,
the value from the parameter “Switch off if brightness value greater than xx LUX” is used as the setpoint.
This object is saved at bus voltage failure and restored at bus voltage recovery.
48
Input switching value (on-off)
On/Off
1 bit
1.001
CWT
If a value (logical 0 or 1) is received via this object, the controller switches off (automatic mode off), because it has been
overwritten from outside.
Only by receiving “logical 1” via object no. 44 will the controller be switched on again (automatic mode on).
49
Input dimming value (on-off)
brighter / darker
4 bit
3.007
CWT
If a value is received via this object, the controller switches off, because it has been overwritten from outside.
Only by receiving “logical 1” via object no. 44 will the controller be switched on again (automatic mode on).
50
Input dimming value (on-off)
value
1 Byte
5.001
CWT
If a value (0-255) is received via this object, the controller switches off, because it has been overwritten from outside.
Only by receiving “logical 1” via object no. 44 will the controller be switched on again (automatic mode on).
51
Switching (on-off)
On
1 bit
1.001
CWT
This object is one of the outputs of the two-
point controller. It sends the value “On” if the brightness is below the defined
brightness
value in a given period of time.
52
Switching (on-off)
Off
1 bit
1.001
CWT
This object is one of the outputs of the two-
point controller. It sends the value “Off” if the brightness is below the defined
brightness value in a given period of time.