PD00D01KNX
– Product Handbook
Eelectron Spa
Via Claudio Monteverdi 6, I-20025 Legnano (MI), Italia
Tel +39 0331.500802 - Fax +39 0331.564826
[email protected] www.eelectron.com
C.F. e P.IVA 11666760159 - Capitale sociale: 800.000,00 interamente versato
Tribunale di Milano 359157-8760-07 - CCIAA Milano 1486549
PD00D01KNXFI00030103.DOCX
27/42
Second telegram (D)
On
Off
8-bit value
scene recall
16-bit value (decimal)
16-bit value (temperature)
16-bit value (brightness)
This parameter is visible only if the preceding pa
rameter “Send second telegram (D)” is set to “Yes”.
This determines the format of the second telegram (D).
Value
[0 … 255]
0 - 255,
0
This parameter is visible only if the precedin
g parameter “Second telegram (D)” is set to “8-bit value”.
This sets the 8-bit value to be sent in the range 0
– 255.
Scene number
scene 1
, scene 2, … scene 64
This parameter is visible only if the precedi
ng parameter “Second telegram (D)” is set to “scene recall”.
This parameter determines the number of the 8-bit scene to be called up.
Value
[0 … 65535]
0 - 65535,
0
This parameter is visible only if the precedi
ng parameter “Second telegram (D)” is set to “16-bit value (decimal).”
This sets the 16-bit value to be sent in the range 0
– 65535.
Value
0.0°C / 32F; 0.5°C / 32F; 1.0°C / 34F; 1.5°C /35F; … 16.5°C /
62F; … 39.5°C/103F; 40.0°C / 104F
This parameter is visible only if the preceding parameter “Second telegram (D)” is set to “16-bit value (temperature)”.
This sets the 16-bit value to be sent in the range 0.0°C / 32F - 40.0°C / 104F.
Value
0LUX; 1LUX; 2LUX; 3LUX; 4LUX; 5LUX; 7LUX; 10LUX; 20LUX;
50LUX; 100LUX; 150LUX; 200LUX; 250LUX; 300LUX; 350LUX;
400LUX; 450LUX;
500LUX
; 550LUX; 600LUX; 650LUX; 700LUX;
750LUX; 800LUX; 850LUX; 900LUX; 950LUX; 1000LUX;
2000LUX
This parameter is visible only if the preceding parameter “Second telegram (D)” is set to “16-bit value (brightness)”.
This sets the 16-bit value to be sent in the range 0 LUX - 2000 LUX .
Send second telegram (D) cyclically
no
1 second
5 seconds
10 seconds
30 seconds
1 minute
If you want cyclical sending after a motion is detected, then this parameter must be set to the corresponding value.
Send telegram (C) [and D] after bus voltage recovery
no
yes
This parameter determines whether telegram C and (if configured) telegram D are also sent automatically after bus voltage recovery..
Dead time after end of detection
[0 … 59 Seconds]
0 - 59,
5
The dead time is used to protect the actuator that is connected to the presence detector. If a motion occurs in the dead time, the
presence detector does not switch on.
Note 1: The dead time should be longer than the delay time between telegrams C and D, because otherwise telegram D may fail.
Note 2: Because the sensor is enabled internally for approximately 3 seconds after detecting a motion, it can be that a motion detected
during the dead time also triggers a telegram. This is the case if the motion is detected during the last 3 seconds of the dead time. To
guarantee that the dead time is effective, it should be chosen to be as large as possible.
Dead time is also applied for extension input
no
yes
If the dead time is configured such that it also acts on the secondary device, then a trigger received from the secondary device is
“interim stored” by the detector. The corresponding telegrams A to D will be sent after the dead time has elapsed.
If the parameter is set to “No”, then the triggers received from the secondary device, take effect immediately.