PD00D01KNX
– Product Handbook
Eelectron Spa
Via Claudio Monteverdi 6, I-20025 Legnano (MI), Italia
Tel +39 0331.500802 - Fax +39 0331.564826
[email protected] www.eelectron.com
C.F. e P.IVA 11666760159 - Capitale sociale: 800.000,00 interamente versato
Tribunale di Milano 359157-8760-07 - CCIAA Milano 1486549
PD00D01KNXFI00030103.DOCX
21/42
Value
0.0°C / 32F; 0.5°C / 32F; 1.0°C / 34F; 1.5°C /35F; …
16.5°C /
62F
; … 39.5°C/103F; 40.0°C / 104F0.0°C / 32F; 0.5°C / 32F;
1.0°C / 34F; 1.5°C /35F; …16.5°C / 62F; … 39.5°C/ 103F; 40.0°C
/ 104F
This parameter is visible only if the precedi
ng parameter “Second telegram (D)” is set to “16-bit value (temperature).”
This sets the 16-bit value to be sent in the range 0.0°C / 32F - 40.0°C / 104F0.0°C / 32F - 40.0°C / 104F.
Value
0LUX; 1LUX; 2LUX; 3LUX; 4LUX; 5LUX; 7LUX; 10LUX; 20LUX;
50LUX; 100LUX; 150LUX; 200LUX; 250LUX; 300LUX; 350LUX;
400LUX; 450LUX;
500LUX
; 550LUX; 600LUX; 650LUX; 700LUX;
750LUX; 800LUX; 850LUX; 900LUX; 950LUX; 1000LUX;
2000LUX
This parameter is visible only if the preceding
parameter “Second telegram (D)” is set to “16-bit value (brightness).”
This sets the 16-bit value to be sent in the range 0 LUX - 2000 LUX .
Send second telegram (D) cyclically
no
1 second
5 seconds
10 seconds
30 seconds
1 minute
This parameter determines whether telegram C and (if configured) telegram D are also sent automatically after bus voltage recovery.
Dead time after end of detection
(in sec.)
0 - 59,
5
The dead time is used to protect the actuator that is connected to the motion detector. If a motion occurs in the dead time, the motion
detector does not switch on.
Note 1: The dead time should be set to a longer time than the delay time between telegrams C and D, because otherwise telegram D
may fail.
Note 2: Because the sensor is enabled internally for approximately 3 seconds after detecting a motion, it can be that a motion detected
during the dead time also triggers a telegram. This is the case if the motion is detected during the last 3 seconds of the dead time. To
guarantee that the dead time is effective, it should be chosen to be as large as possible.
Dead time is also applied for extension input
no
yes
If the dead time is configured such that it also acts on the secondary device, then a trigger received from the secondary device is
“interim
stored” by the detector. The corresponding telegrams A to D will be sent after the dead time has elapsed.
If the parameter is set to “No”, then the triggers received from the secondary device, take effect immediately.
Communication objects motion detector
Obj.-no.
Object name
Function
Type
Flags
4
End of Motion, D
value
1 Byte/2 Byte
CRWT
On/Off
1 bit
recall
1 Byte
Depending on the setting, this object sends one of the following values to the bus at the end of a detected motion or upon external
triggering:
Switch On/Off - DPT 1.001
8-bit value (decimal) (0
– 255) - DPT 5.001
16-bit value (decimal) (0 - 65 535) - DPT 7.001
16-bit value (temperature) (0.0°C / 32F - 40.0°C / 104F) - DPT 9.001
16-bit value (brightness) (0LUX
– 2000LUX) - DPT 9.004
8-bit scene recall
–DPT 17.001
Telegram D is sent after telegram C, if this has been configured. The delay time between C and D is also configurable.
5
Motion, Overshoot Time
value
2 Byte
8.001
CRW
time 1 = 0 / time 2 =
1
1 bit
1.001
This object controls the detector overshoot time. Depending on configuration either a current value (DPT 8.001,
resolution 1 second) or one of the preconfigured overshoot times (overshoot time 0 or overshoot time 1) is selected.
This object is saved at bus voltage failure and restored at bus voltage recovery.