HVAC-Presence detector
Parameter
Parameter
Setting
Lock HVAC sensor via comm.-object
no
Yes, if locking object = 0
Yes, if locking object = 1
This parameter determines how the value of the locking object is analyzed.
Interval time for HVAC-Presence detection
(minutes)
0
– 15;
5
This parameter determines the time interval in which the motion pulses are counted.
Minimum number of detected motions during interval
time
1
– 50;
3
This parameter determines the number of motions that have to be detected during the monitoring time to meet the criterion for starting
the HVAC presence. This ensures that a HVAC presence starts only if persons remain in the capture area of the detector for a longer
period.
Device works as
single or master device
slave
This parameter determines whether the detector is used as a standalone device or as a master or as a slave in conjunction with other
motion sensors.
Begin of HVAC Presence
The following parameters are visible only if the device is working as a standalone device or as a master (parameter
“Device works as” is set to “Single or master device”).
Parameter
Setting
If HVAC-Presence is detected, send (A)
no telegram
On
Off
8-bit value
scene recall
16-bit value (decimal)
16-bit value (temperature)
16-bit value (brightness)
This parameter determines whether a telegram is sent after a presence is detected and what format the telegram has.
Send second telegram (B)
no
yes
This parameter determines whether a second telegram is sent after a delay to the first.
Value
[0 … 255]
0
– 255,
0
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (A)” is set to “8-bit value.”
This sets the 8-bit value to be sent in the range 0
– 255.
Scene number
scene 1
, scene 2, … scene 64
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (A)” is set to “scene recall”.
This parameter determines the number of the 8-bit scene to be called up.
Value
[0 … 65535]
0
– 65535,
0
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (A)” is set to “16-bit value (decimal)”.
This sets the 16-bit value to be sent in the range 0
– 65535.
Value
0.0°C / 32F; 0.5°C / 32F; 1.0°C / 34F; 1.5°C /35F; … 16.5°C /
62F; … 39.5°C/103F; 40.0°C / 104F
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (A)” is set to “16-bit value (temperature)”.
This sets the 16-bit value to be sent in the range 0.0°C / 32F - 40.0°C / 104F.
Value
0LUX; 1LUX; 2LUX; 3LUX; 4LUX; 5LUX; 7LUX; 10LUX; 20LUX;
50LUX; 100LUX; 150LUX; 200LUX; 250LUX; 300LUX; 350LUX;
400LUX; 450LUX;
500LUX
; 550LUX; 600LUX; 650LUX; 700LUX;
750LUX; 800LUX; 850LUX; 900LUX; 950LUX; 1000LUX;
2000LUX
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (A)” is set to “16-bit value (brightness)”.
This sets the 16-bit value to be sent in the range 0 LUX - 2000 LUX .
Delay for second telegram
[0 … 255 Seconds]
0 - 255,
0
This parameter is visible only if the preceding parameter “Send second telegram (B)” is set to “Yes”.