Overshoot time
The following parameters are visible only if the device is working as a standalone device or as a master (parameter
“Device works as” is set to “Single or master device”).
Parameter
Setting
Timer
one overshoot time
two overshoot times
variable overshoot time
This parameter determines whether the overshoot time is always the same (“One overshoot time”) or can be changed via a bus
telegram (object no. 21).
If “Two overshoot times” are set, then overshoot time 0 or overshoot time 1 can be selected via the telegram. If the “Timer” parameter
is set to “variable overshoot times,” then the telegram can stipulate a value.
Hours
[0 … 23]
0
– 23,
0
Minutes
[0 … 59]
0
– 59,
0
Seconds
[0 … 59]
0
– 59,
10
These parameters determine the minimum time for a detected HVAC presence. At the end of the overshoot time, one or two telegrams
are sent on the bus (configurable). If a HVAC presence has already been detected (overshoot time running) and further motion occurs,
then the overshoot time is restarted.
If the “Timer” parameter described above is set to “Two overshoot times,” then these parameters are available twice (overshoot time 0
and overshoot time 1).
End of HVAC Presence
The following parameters are visible only if the device is working as a standalone device or as a master (parameter
“Device works as” is set to “Single or master device”).
Parameter
Setting
If HVAC-Presence is no longer detected, send (C)
no telegram
On
Off
8-bit value
scene recall
16-bit value (decimal)
16-bit value (temperature)
16-bit value (brightness)
This parameter determines whether a telegram or which telegram is sent, if no further HVAC presence has been detected by the end of
the overshoot time.
Send second telegram (D)
no
yes
This parameter determines whether a second telegram is sent after a delay to the first.
Value
[0 … 255]
0
– 255,
0
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (C)” is set to “8-bit value.”
This sets the 8-bit value to be sent in the range 0
– 255.
Scene number
scene 1
, scene 2, … scene 64
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (C)” is set to “scene recall”.
This parameter determines the number of the 8-bit scene to be called up.
Value
[0 … 65535]
0
– 65535,
0
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (C)” is set to “16-bit value (decimal)”.
This sets the 16-bit value to be sent in the range 0
– 65535.
Value
0.0°C / 32F; 0.5°C / 32F; 1.0°C / 34F; 1.5°C /35F; … 16.5°C /
62F; … 39.5°C/103F; 40.0°C / 104F
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (C)” is set to “16-bit value (temperature)”.
This sets the 16-bit value to be sent in the range 0.0°C / 32F - 40.0°C / 104F.
Value
0LUX; 1LUX; 2LUX; 3LUX; 4LUX; 5LUX; 7LUX; 10LUX; 20LUX;
50LUX; 100LUX; 150LUX; 200LUX; 250LUX; 300LUX; 350LUX;
400LUX; 450LUX;
500LUX
; 550LUX; 600LUX; 650LUX; 700LUX;
750LUX; 800LUX; 850LUX; 900LUX; 950LUX; 1000LUX;
2000LUX
This parameter is visible only if the preceding parameter “If HVAC presence is detected, send (C)” is set to “16-bit value (brightness)”.
This sets the 16-bit value to be sent in the range 0 LUX - 2000 LUX .
Delay for second telegram
[0 … 255 Seconds]
0 - 255,
0
This parameter is visible only if the preceding parame
ter “Send second telegram (D)” is set to “Yes”.
This determines the time interval between sending the first telegram (C) and the second telegram (D).