Setpoint abs. (DPT 9.004) (continuous)
value in LUX
2 Byte
9.004
CRWT
Via this object the setpoint for the constant light level control is set. Until the first value is received the value of the parameter
“Maximum setpoint in LUX” is used as default value.
Note 1: The currently valid control setpoint is sent via this object onto the bus on change of value, thus allowing a visualization to
display the current value.
Note 2: When the setpoint value changes the control process may be active dependent on the determined calibration curve even if the
actual value is within the range defined by the setpoint and the hysteresis.
Note 3: On bus voltage recovery the value of this object is sent automatically.
Note 4: The setpoint value is limited by the configuration settings for minimum / maximum set point value.
Note 5: On reception of 0 the set point value is not changed.
56
Setpoint rel. (DPT 3007) (continuous)
brighter / darker
4 bit
3.007
CRW
Via this object the setpoint can be changed relative to the current value. The controller increments or decrements the
internal setpoint
every second by a dimming value set via parameter, if “dimming with stop telegram” is used.
Note1: The controller can process relative changes of the setpoint only every second. When e.g. two ¼-brighter
dimming telegrams are
received within 200ms then both are joined together. The result is one dimming brighter command with about 56%
increase.
Note 2: The setpoint value is limited by the configuration settings for minimum / maximum set point value.
57
Control stop, switching value (continuous)
On/Off
1 bit
1.001
CWT
When a value is received via this object then the controller changes its state to ”inactive”. In this state the controller is
passive, i.e. no control commands are sent onto the bus.
58
Control stop, dimming (continuous)
brighter / darker
4 bit
3.007
CWTU
When a value is received via this object then the controller changes its state to ”inactive”. In this state the controller is
passive, i.e. no control commands are sent onto the bus.
59
Control stop, dimming value (continuous)
dimming value
1 Byte
5.001
CWTU
When a value is received via this object then the controller changes its state to ”inactive”. In this state the controller is
passive, i.e. no control commands are sent onto the bus.
60
Output switching Master (continuous)
On/Off
1 bit
1.001
CWT
Via this object the controller sends on and off control commands to the main lighting group. It sends the value “On”
when the brightness is below the defined brightness setpoint for a defined time. It sends the value “Off” when the
controller received a lo
gical “0” via object 53 or when the controller changes from the state “active” to the state “standby”
(see parameter “Time until controller automatically switches off”.
61
Output dimming value (Master)
dimming value
1 Byte
5.001
CWTU
Via this object the controller sends the dimming values for the main lighting group.
62
Master status dimming (continuous)
dimming value
1 Byte
1.001
CWTU
Via this object the current dimming value of the dimming actuator for the main lighting group (master) can be read.
63
Output switching Slave1 (continuous)
On/Off
1 bit
1.001
CWT
Via this object the controller sends on and off control commands to the first additional lighting group. It sends the value
“On” when the brightness is below the defined brightness setpoint for a defined time. It sends the value “Off” when the
controller received a logical “0” via object 53 or when the controller changes from the state “active” to the state
“standby”.
64
Output dimming value Slave1 (continuous)
dimming value
1 Byte
5.001
CWT
Via this object the controller sends the dimming values for the first additional lighting group.
65
Output switching Slave2 (continuous)
On/Off
1 bit
1.001
CWT
Via this object the controller sends on and off control commands to the second additional lighting group. It sends the
value “On” when the brightness is below the defined brightness setpoint for a defined time. It sends the value “Off” when
the controller received a logical
“0” via object 53 or when the controller changes from the state “active” to the state
“standby”.