E93.1803.901 HW
58
10.1.7
E
XAMPLE
B:
T
WIN PIPE SYSTEM WITH CONCENTRIC ROOF TERMINAL
Calculation example with given lengths: checking resistance
Water heater type:
CB 125
Flue gas
Diameter: 100 mm
Number
Pa
Pa total
Straight tube /m
total
6
6.0
36.0
Bend
90°
2
21.9
43.8
Roof terminal
concentric
100/150
1
66.7
66.7
Adaptor conc./par.
100-100 >
100/150
1
0.9
0.9
Total resistance flue gas outlet:
147.4
A
ir
su
pp
ly
Diameter: 100 mm
Number
Pa
Pa total
Straight tube /m
total
6
6.9
41.4
Bend
90°
2
25.3
50.6
Roof terminal
concentric
100/150
1
92.4
92.4
Adaptor conc./par.
100-100 >
100/150
1
83.8
83.8
Total resistance air supply:
268.2
Total resistance flue gas outlet and air supply:
415.6
The total resistance is more than 200 Pa.
This flue gas / air supply system is NOT functional.
NOTE: ECO specific resistance values are used in this example.
Flue and air pipes of other suppliers can have other values