E93.1803.901 HW
54
C83
Closed
Air supply
from outside
* Separate air supply duct from external wall.
*Flue gas discharge through individual or
shared flue ducting built into the building.
* Air supply inlet and flue gas outlet at different
air pressure zones.
* Condensate is not allowed to go to the boiler.
* Technical data:
nominal T
flue gas
85 °C
nominal Q
fluegas
see 3.2.1
1)
maximum T
fluegas
90 °C
min. load T
fluegas
35 °C
min. load Q
fluegas
see 3.2.1
1)
nominal % CO
2
see 3.2.1
1)
1) technical specifications datasheet
* Flue duct: Material: PP or SS
CE approved
C93
Closed
Air supply
from outside
Type C93 . A type C9 appliance incorporating a
fan upstream of the combustion cham-
ber/heat exchanger.
Minimum required diameter/ cross section area:
boiler
diameter
area
CB 85, 105, 125
100 mm
7854 mm
2
CB 155
150 mm
17671 mm
2
Air inlet
Flue outlet
Air inlet