18 COMMISSIONING THE WATER HEATER
First: flushing the water heater with water
After installation of the water heater the first step, before commissioning, is to flush the water heater and the whole
installation with fresh water to remove pollution, debris and other materials that might cause a blocking. This must
also be done with installations, where only the water heater is replaced.
Existing and new systems must be cleaned with a hydronic system cleaner. System cleaner must be drained and
thoroughly flushed with clean water to remove any residual cleaner, prior to installing a new water heater. NEVER
leave a system cleaner for longer than recommended by the manufacturer of the cleaner. Never put system cleaner
inside the water heaters heat exchanger.
Second: filling & venting the water heater and the system
After flushing the water heater and the installation the system can be filled with fresh water.
The water heater has an automatic air vent situated inside the water heater. This vent is always open and the
venting outlet goes via a plastic tube through the bottom to the outside.
During the commissioning, make sure no water can enter the water heater and make contact with the electrical
parts.
Third: check the water flow
Before starting the water heater ensure the pump is installed and operating correctly and that there are no ob-
structions or closed valves that could prevent water flow through the heat exchanger.
Mounting Condensate Trap
When mounting the bottom part of the condensate trap, before commissioning the water heater and/or after
maintenance, it must
ALWAYS
be completely filled with water.
This is a safety measure: the water in the condensate trap keeps the flue gases
from leaking out of the heat exchanger via the condensate drain.
When the water heater receives a heat demand the electronics will start the operation of the water heater. Before
the water heater is used, the water heater must be adjusted and set at the minimum and maximum load.
NOTICE:
Always ensure the water heater pump is functioning correctly and that there is flow through the heat
exchanger after working on the water heater or system.
WARNING
The condensate trap must al-
ways be filled to the edge with
water, before replacing to the
unit.
WARNING
Summary of Contents for CB 105 HW
Page 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Page 70: ...E93 1803 901 HW 71...
Page 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Page 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Page 128: ...E93 1803 901 HW 129...
Page 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Page 130: ...E93 1803 901 HW 131...
Page 145: ......
Page 146: ......