E93.1803.901 HW
50
Water heater categories - types of flue gas systems.
For C43 and cascade see manuals at the suppliers website:
Type according EN 15502-2-1: 2012
Performance
Description
C10(3)
Closed or open
Air supply from
out-side or room
Over pressure common flue system:
* Flue gas discharge through individual or shared
flue ducting built into the building.
* Air supply inlet and flue gas outlet
* Condensate is not allowed to go to the boiler.
* Technical data:
nominal T
flue gas
85 °C
nominal Q
fluegas
see 3.2.1
1)
maximum T
fluegas
90 °C
min. load T
fluegas
35 °C
min. load Q
fluegas
see 3.2.1
1)
nominal % CO
2
see 3.2.1
1)
1) technical specifications datasheet
* Flue ducting: Material: PP or SS, CE approved
* max. collector flue pressure 25pa
WARNING:
If other than M&G flue gas materials are
used, please contact your boiler supplier.
C11(3)
Closed or open
Air supply from
out-side or room
Over pressure common flue system:
* Flue gas discharge through individual or shared
flue ducting built into the building.
* Air supply inlet and flue gas outlet
* Condensate is not allowed to go to the boiler.
* Technical data:
nominal T
flue gas
85 °C
nominal Q
fluegas
see 3.2.1
1)
maximum T
fluegas
90 °C
min. load T
fluegas
35 °C
min. load Q
fluegas
see 3.2.1
1)
nominal % CO
2
see 3.2.1
1)
1) technical specifications datasheet
* Flue ducting: Only M&G multi PP and SS ac-
cording to the C11 flue gas manual.
* max. collector flue pressure 85pa
Check the C11 Common Flue gas manual to cal-
culate the flue gas system.
C(12)3
Closed
Air supply from
out-side
Over pressure common flue system:
* Flue gas discharge through individual or shared
flue ducting built into the building.
* Air supply inlet and flue gas outlet
* Condensate is not allowed to go to the boiler.
* Technical data:
nominal T
flue gas
85 °C
nominal Q
fluegas
see 3.2.1
1)
maximum T
fluegas
90 °C
min. load T
fluegas
35 °C
min. load Q
fluegas
see 3.2.1
1)
nominal % CO
2
see 3.2.1
1)
1) technical specifications datasheet
* Flue ducting: Material: PP or SS, CE approved
* max. collector flue pressure 25pa
Summary of Contents for CB 105 HW
Page 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Page 70: ...E93 1803 901 HW 71...
Page 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Page 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Page 128: ...E93 1803 901 HW 129...
Page 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Page 130: ...E93 1803 901 HW 131...
Page 145: ......
Page 146: ......