Instructions for
VSR-Series Type 5HK
Vacuum Motor Starter
IB01301027E
Page 5
Page 5
Page 5
Page 5
Page 5
Effective: May 2008
Effective: May 2008
Effective: May 2008
Effective: May 2008
Effective: May 2008
IB01301027E
SECTION 1: INTRODUCTION
The purpose of this book is to provide instructions for receiving,
handling, storage, installation, operation and maintenance of Type
5HK-VSR Vacuum Motor Starter Replacement Units. They are
horizontal drawout type removable interrupting elements for use in
existing 5HK Metal-Clad Switchgear. 5HK-VSR Motor Starter
Replacements provide reliable control, protection and performance,
with ease of handling and maintenance. Like ratings are inter-
changeable with each other.
1.1 AVAILABLE 5HK-VSR MOTOR STARTER REPLACEMENTS
Refer to Table 1.1
SATISFACTORY PERFORMANCE OF THESE VACUUM MOTOR STARTER
REPLACEMENT UNITS IS CONTIGENT UPON PROPER APPLICATION,
CORRECT INSTALLATION AND ADEQUATE MAINTENANCE. THIS
INSTRUCTION BOOK MUST BE CAREFULLY READ AND FOLLOWED IN
ORDER TO OBTAIN OPTIMUM PERFORMANCE FOR LONG USEFUL
LIFE OF THE VACUUM MOTOR STARTER.
TYPE 5HK-VSR VACUUM MOTOR STARTER REPLACEMENT UNITS ARE
PROTECTIVE DEVICES, AS SUCH, THEY ARE MAXIMUM RATED
DEVICES. THEREFORE, THEY SHOULD NOT UNDER ANY CIRCUM-
STANCE BE APPLIED OUTSIDE THEIR NAMEPLATE RATINGS.
Table 1.1 - 5HK-VSR Vacuum Motor Starter Replacement Unit Availability and Interchangeability
WARNING
Original Breaker Type
(Does Not Include MOC
Operator or Blown Fuse
Protection)
MV-VSR Breaker
to Motor Starter
Replacement Unit
Rated Max.
Volts kV
Contactor
Amps
Max.
Fuse
Rating
Amps
Short
Circuit
Rating
kA
5HK-250-1200A
5HK-VSR-250
4.76
400
230 / 390
50
5HK-350-1200A
5HK-VSR-350
4.76
400
230 / 390
50