Instructions for
VSR-Series Type 5HK
Vacuum Motor Starter
IB01301027E
Page 9
Page 9
Page 9
Page 9
Page 9
Effective: May 2008
Effective: May 2008
Effective: May 2008
Effective: May 2008
Effective: May 2008
IB01301027E
Outdoor storage is
NOT
recommended. If unavoidable, the outdoor
location must be well drained and a temporary shelter from sun,
rain, snow, corrosive fumes, dust, dirt, falling objects, excessive
moisture, etc. must be provided. Containers should be arranged to
permit free circulation of air on all sides and temporary heaters
should be used to minimize condensation. Moisture can cause
rusting of metal parts and deterioration of high voltage insulation. A
heat level of approximately 400 watts for each 100 cubic feet of
volume is recommended with the heaters distributed uniformly
throughout the structure near the floor.
Indoor storage should be in a building with sufficient heat and
circulation to prevent condensation. If the building is not heated, the
same general rule for heat as for outdoor storage should be applied.
Table 3.1 - Maximum Weight by Starter Type
Circuit Breaker Type
Max. Amperes
LBs.
5HK-VSR
390
405
230
390
3.4 5HK-VSR APPROXIMATE WEIGHTS
Refer to Table 3.1