Eaton VSR Series Instructions Manual Download Page 23

For more information visit: www.eaton.com

www.eaton.com

www.eaton.com

www.eaton.com

www.eaton.com

Instructions for
VSR-Series Type 5HK
Vacuum Motor Starter

IB01301027E

Page  21

Page  21

Page  21

Page  21

Page  21

Effective:  May 2008

Effective:  May 2008

Effective:  May 2008

Effective:  May 2008

Effective:  May 2008

IB01301027E

of plugging or jogging which may require more frequent replace-
ment. Verification of contact wear can be made by following the
procedure below.

The overtravel gap for a new starter is .080" and is set at the
factory. As the contacts wear the overtravel is reduced. The SL
interrupter design allows for .080" wear before replacement is
required. To verify that the contacts are not worn beyond their
allowable limits, close the contactor with rated control power. Insert
the .020" contactor wear gauge, p/n 5259C11H01, between the
operating plate and the washer on the lower insulator stem of each
pole. Refer to Figure 

6-1

. If the gauge cannot be freely inserted on

each pole, all three interrupters must be replaced. Refer to the
section 5.3.1 for instructions on replacing the interrupters.

6.4  INSULATION INTEGRITY CHECK

PRIMARY CIRCUIT:

The integrity of primary insulation may be checked by the AC high
potential test.  The test voltage is 15kV, RMS, 60Hz. Conduct the
test as follows:

Close the starter.  Connect the high potential lead of the test
machine to one of the phases of the starter.  Connect the remaining
two phases and starter frame to ground.  Start the machine with
output potential at zero and increase to the test voltage.  Maintain
the test voltage for one minute.  Repeat for the remaining phases.
Successful withstand indicates satisfactory insulation strength of
the primary circuit.

Open the starter.  Connect the high potential lead of the test
machine to one of the poles of the starter.  Connect the remaining
poles and starter frame to ground.  Start the machine with output
potential at zero and increase to the test voltage.  Maintain the test
voltage for one minute.  Repeat for the remaining five poles.
Successful withstand indicates satisfactory insulation strength of
the primary circuit.

If a DC high potential machine is used, make certain that the peak
voltage does not exceed the peak of the corresponding AC RMS
test voltage.

SECONDARY CIRCUIT:

Connect all points of the secondary disconnect pins with a shorting
wire.  Connect this wire to the high potential lead of the test
machine.  Ground the starter frame.  Starting with zero, increase
the voltage to  1125 RMS, 60 Hz.  Maintain the voltage for one
minute.  Successful withstand indicates satisfactory insulation
strength of the secondary control circuit.  Remove the shorting
wire.

6.5  CONTACT RESISTANCE CHECK

Testing that measures the contact resistance of the VI’s is not
recommended since the results can vary widely on good contacts.
If a resistance check is performed, the best results will be with a
test module that will force 10 amps through the contacts while
measuring resistance. The resistance should not exceed the
factory test levels by more than 15%.

Do not use a 100 Amp source. Test sets with output
exceeding 10 Amps can damage the fuse elements

NOTICE

Summary of Contents for VSR Series

Page 1: ...it www eaton com www eaton com www eaton com www eaton com www eaton com IB01301027E IB01301027E Instructions for VSR Series Breaker To Vacuum Starter Replacement For Type 5HK Breakers 5HK VSR Vacuum...

Page 2: ......

Page 3: ...NSAS THEYMAYBEAPPLIEDTOTHISTYPEOFEQUIPMENTMUSTBE STRICTLYADHEREDTO THESEVACUUMMOTORSTARTERREPLACEMENTSAREDESIGNEDTO BEINSTALLEDPURSUANTTOTHENATIONALELECTRICALCODE NEC SERIOUSINJURY INCLUDINGDEATH CANR...

Page 4: ...13 4 5 INTERRUPTERWEARCHECK 13 4 6 PRIMARYCIRCUITRESISTANCE 13 4 7 ELECTRICALOPERATIONSCHECK 13 4 8 INSERTIONPROCEDURE 13 4 9 REMOVALPROCEDURE 15 SECTION5 DESCRIPTIONANDOPERATION 1 6 5 1 CONTACTOROPE...

Page 5: ...2008 Effective May 2008 Effective May 2008 IB01301027E Tables T able1 1 5HK VSRVacuumMotorStarterReplacementUnitAvailabilityandInterchangeability 5 T able1 2 5HK VSRVacuumMotorStarterReplacementUnitDi...

Page 6: ...nts 17 Figure 5 2 SL Rear View Major Components 17 Figure 5 3 SL Contactors Assembly 18 Figure 5 4 Secondary Contact Block of 5HK VSR 19 Figure 5 5 5HK VSR Code Plate 19 Figure 5 6 5HK VSR Cell Code P...

Page 7: ...ratings are inter changeable with each other 1 1 AVAILABLE5HK VSRMOTORSTARTERREPLACEMENTS Refer to Table 1 1 SATISFACTORYPERFORMANCEOFTHESEVACUUMMOTORSTARTER REPLACEMENTUNITSISCONTIGENTUPONPROPERAPPL...

Page 8: ...01027E Page 6 Page 6 Page 6 Page 6 Page 6 Effective May 2008 Effective May 2008 Effective May 2008 Effective May 2008 Effective May 2008 T able1 2 5HK VSRVacuumMotorStarterReplacementUnitDimensionsinI...

Page 9: ...y y y y y Alwaysremovethestarterfromtheenclosurebefore performinganymaintenance Failuretodosocouldresult inelectricalshockleadingtodeath severepersonnelinjury orpropertydamage y y y y y Proper persona...

Page 10: ...g Dolly Optional item used to help maneuver starter when out of structure Contact Wear Gauge Optional item used to check contact wear Style 5259C11H01 Lifting Sling Optional item used to lift the star...

Page 11: ...s should be arranged to permit free circulation of air on all sides and temporary heaters should be used to minimize condensation Moisture can cause rusting of metal parts and deterioration of high vo...

Page 12: ...ter IB01301027E IB01301027E Page 10 Page 10 Page 10 Page 10 Page 10 Effective May 2008 Effective May 2008 Effective May 2008 Effective May 2008 Effective May 2008 Figure 3 3 Front External View of 5HK...

Page 13: ...5HK Vacuum Motor Starter IB01301027E Page 11 Page 11 Page 11 Page 11 Page 11 Effective May 2008 Effective May 2008 Effective May 2008 Effective May 2008 Effective May 2008 IB01301027E Figure 3 4 Rear...

Page 14: ...he starter for any damage that occurred during shipment storage and installation Set the dip switches in the coil control board for the proper control voltage and dropout time Figures 4 1 and 4 2 and...

Page 15: ...bolted in position as shown in Figures 3 3 and 3 4 before inserting the starter into the cell EXAMINE THE INSIDE OF THE CELL BEFORE INSERTING THE STARTER FOR EXCESSIVE DIRT OR ANYTHINGTHAT MIGHT INTER...

Page 16: ...ce by the levering arms resting completely against the positive stops located on the starter truck This is the fully connected position Figure 4 6 The position indicator on the starter will show TEST...

Page 17: ...m Instructions for VSR Series Type 5HK Vacuum Motor Starter IB01301027E Page 15 Page 15 Page 15 Page 15 Page 15 Effective May 2008 Effective May 2008 Effective May 2008 Effective May 2008 Effective Ma...

Page 18: ...M coils establish a magnetic field within the interrupter during fault conditions The field disperses the arc during fault current interruption allowing the contactor to interrupt a very high fault c...

Page 19: ...3 Moving Armature Plate Optional Aux Contacts Stop Assembly Baseplate 8 9 10 11 12 13 14 Frame Front Mounting Holes 4 Operating Plate Main Shaft Aux Contact Operating Lever Standard Aux Contacts Coil...

Page 20: ...nt are recessed to prevent accidental short circuiting of the control circuits These secondary disconnects mate in both the operating and test positions No special jumper is required Mechanical stops...

Page 21: ...H MOC SWITCH Figure 5 4 Secondary Contact Block of 5HK VSR Figure 5 5 5HK VSR Code Plate WARNING Figure 5 7 5HK VSR Ground Contact existing levering system located in the existing HK assembly structur...

Page 22: ...NCE BETWEENTHE OPEN CONTACTS THE LEVELS OF RADIATION GENERATED AT THE RECOMMENDED TEST VOLTAGES AND NORMAL CONTACTOR OPEN GAP SPACING ARE EXTREMELY LOW HOWEVER AS A PRECAUTIONARY MEASURE IT IS RECOMME...

Page 23: ...achine with output potential at zero and increase to the test voltage Maintain the test voltage for one minute Repeat for the remaining phases Successful withstand indicates satisfactory insulation st...

Page 24: ...to housing Figure 7 2 4 Remove bolt and shunt supports securing end of lower terminal to housing Figure 7 3 5 Remove the bolt securing VI to upper terminal Figure 7 4 6 Hold insulator down and rotate...

Page 25: ...ould compress the return spring and prevent the proper force from being applied to the operating plate on opening The rear locknut for the return bolt should then be tightened on the back of the angle...

Page 26: ...mps through the contacts for a short period of time If one or more of the auxiliary contacts fail it is recommended that the complete contact block assembly be replaced Disconnect wiring to each conta...

Page 27: ...latch coil is energized the coil may be faulty To determine if the coil has the proper resistance connect an ohmmeter across the coil leads where they are connected to the bridge rectifier Refer to Ta...

Page 28: ...etween Roller Bearing and Cam to 5mm 020 used they will extend through the armature plate and prevent the contactor from closing and sealing when the main coils are energized 3 Locate latch assembly i...

Page 29: ...u u c a V 3 0 G 8 5 A 7 4 1 2 d r a o B l o r t n o C l i o C 4 0 G 8 5 A 7 4 1 2 C N 2 O N 2 t i K t c a t n o C y r a i l i x u A 5 0 G 8 5 A 7 4 1 2 r o t c a t n o C d e h c t a L r o f C N 3 O N...

Page 30: ......

Page 31: ......

Page 32: ...ILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CON TAINED HEREIN In no event will Eaton Corporation be respons...

Reviews: