1 DA1 device series
1.10 Maintenance and inspection
38
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
1.10 Maintenance and inspection
DA1 variable
frequency drives
are maintenance-free, provided that the
general rating data, as well as the technical data for the specific models in
use, is observed. Please note, however, that external influences may effect
the operation and lifespan of a DA1 variable frequency drive.
Because of this, we recommend inspecting the devices on a regular basis
and carrying out the following maintenance activities at the specified
intervals.
Table 2: Recommended maintenance
There are no plans for replacing or repairing individual components of DA1
variable frequency drives.
If the variable frequency drive DA1 in sizes FS2 or FS3 (IP20, IP66) is
damaged or destroyed due to external influences, a repair is not possible.
For sizes FS4 to FS8 a conditional repair is possible by qualified and certified
workshops (
section 1.13, “Service and warranty”).
Dispose of the device according to the applicable environmental laws and
provisions for the disposal of electrical or electronic devices.
Maintenance measures
Maintenance interval
Clean cooling vents
If necessary
Check that the fan is working properly
6 - 24 months (depending on the environment)
Check the filters in the control panel door
(see the manufacturer's specifications)
6 - 24 months (depending on the environment)
Check all earth connections to make sure they
are intact
On a regular basis, at periodic intervals
Check the tightening torques of the terminals
(control terminals, power terminals)
On a regular basis, at periodic intervals
Check connection terminals and all metallic
surfaces for corrosion
6 - 24 months; when stored, no more than 12 months later
(depending on the environment)
Motor cables and shielding connection (EMC)
According to the manufacturer's specifications, no later than 5
years
Charge capacitors
12 months
(