6 Specifications
6.2 Specific rated operational data
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
149
6.2.2 DA1-32… series
Size
Symbol
Unit
4D3
7D0
011
018
024
024
Rated operational current
I
e
A
4.3
7.0
10.5
18
24
24
Overload current for 60 s every 600 s
I
L
A
6.45
10.5
15.75
27
36
36
Apparent power at rated operation
230 V
S
kVA
1.71
2.79
4.18
7.17
9.56
9.56
240 V
S
kVA
1.79
2.91
4.36
7.48
9.98
9.98
Rated motor output
230 V
P
kW
0.75
1.5
2.2
4.0
5.5
5.5
230 V
P
HP
1
2
3
5
7.5
7.5
Power input side (primary side):
Number of phases
three-phase
Rated voltage
U
LN
V
200 V - 10 % - 240 V +10 %, 50/60 Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
Input current (phase current)
I
LN
A
5.1
8.3
12.6
21.6
29.1
29.1
Minimum braking resistor
R
B
Ω
100
50
35
20
20
20
Switching frequency (pulse frequency)
Factory default setting
f
PWM
kHz
16
16
16
16
16
16
Settings range
f
PWM
kHz
4 - 32
4 - 32
4 - 32
4 - 32
4 -16
4 - 16
Maximum leakage current to earth (PE), without motor
I
PE
mA
1.73
1.73
1.73
0.93
0.93
1.42
Efficiency
η
0.95
0.96
0.96
0.96
0.97
0.97
Heat dissipation at I
e
P
V
W
39.75
61.5
90.2
160
170.5
170.5
Frame size
FS2
FS2
FS2
FS3
FS3
FS4