3 Installation
3.6 Electrical Installation
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
115
Figure 83: Preventing the screen from becoming unbraided
Alternatively, in addition to the broad area cable clip, you can also twist the
screen braid at the end and connect it to the protective ground with a cable
lug. To prevent EMC disturbance, this twisted screen connection should be
made as short as possible.
Prevent the screen from becoming unbraided at the other end of the control
cable, e.g. by using a rubber grommet. The screen braid must not make any
connection with the protective ground here because this would cause
problems with an interference loop.
15 mm
(0.59’
’)
PES