4 Operation
4.3 Commissioning with control signal terminals (default settings)
132
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
Connection example for three-phase motor
▶
For simple commissioning with the preset default settings, connect the
variable frequency drive as shown in the connection example above.
The potentiometer should have a fixed resistance (connection to control
signal terminals 5 and 7) of at least 1 k
Ω
, up to a maximum of 10 k
Ω
.
A standard fixed resistance of 4.7 k
Ω
is recommended.
Make sure that the enable contacts (FWD/REV) are open and the STO is
connected correctly before switching on the mains voltage.
When the specified supply voltage is applied at the mains connection
terminals (L1/L, L2/N, L3), the switched-mode power supply unit (SMPS) in
the DC link will be used to generate the control voltage and light up the
7-segment LED display (STOP).
At this point, the variable frequency drive will be ready for operation (correct
operating status) and in Stop mode.
Connection example for three-phase motor
Terminal
Name
L1/L
Single-phase mains
connection
(DA1-12…)
Three-phase mains
connection(DA1-3…)
L2/N
L3
–
Ground connection
1
Control v24 V (output, maximum 100 mA)
2
FWD, Start
enable clockwise rotating field
3
REV, Start
enable left rotating field
U
Connection for three-phase ac motor
(three-phase motor)
V
W
5
Control v10 V (output, maximum 10 mA)
6
Frequency reference value f-Set (Input 0 – +10 V)
7
Reference potential (0 V)
12
Safe Torque Off +
13
Safe Torque Off -
PE
PE
W
V
U
M
3 ~
6
7
5
1
2
3
+24 V
FWD
0...+10 V
0 V
+10 V
L3
L1/L L2/N
L
N
L3
L1
L2
REV
f-Soll
12
13
STO+
STO-
→
If the connections for the setpoint value potentiometer cannot
be clearly allocated with terminals 5, 6 and 7, you should set the
potentiometer to about 50 % before giving the start
enable
(FWD/REV) for the first time.