3 Installation
3.6 Electrical Installation
100
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
3.6.1.1 Connection terminals on frame sizes FS2 and FS3 with IP20
Table 7: Connection terminals (FS2, FS3)
Connection terminals
Description
Connection with single-phase supply voltage (230 V):
• DA1-12… (200 - 240 V)
Connection with three-phase supply voltage:
• DA1-32… (200 - 240 V)
• DA1-34… (380 - 400 V)
• DA1-35… (500 - 600 V)
Motor connection for three-phase motors:
(motor voltage = supply voltage)
• DA1-12…
• DA1-32…
• DA1-34…
• DA1-35…
optional: internal or external braking resistor (R
B
)
→
DC+ and DC- for DC link coupling or if the device is being
supplied with DC voltage.
To do this, the terminal screw cover needs to be knocked out.
DC-
L1/L
L2/N
L3
⏚
L
N
PE
DC-
L1/L
L2/N
L3
L1
L2
PE
L3
PES
DC+
BR
U
V
W
⏚
R
B
M
3