Eaton 9140 UPS (7.5–10 kVA) User's Guide
S
164201622 Rev 3
www.eaton.com/powerquality
95
Chapter 8
Troubleshooting
The Eaton 9140 is designed for durable, automatic operation and also
alerts you whenever potential operating problems may occur. Usually
the alarms shown by the control panel do not mean that the output
power is affected. Instead, they are preventive alarms intended to alert
the user. Use the following troubleshooting chart to determine the UPS
alarm condition.
Typical Alarms and Conditions
The following table describes typical alarms and conditions; check the
Alarm History through the front panel for a list of active alarms. If an
alarm appears with a service code, please contact the Help Desk (see
page 99).
Alarm or Condition
Possible Cause
Action
On Battery
LED is on.
1 short beep every 5 seconds.
A utility failure has occurred and the
UPS is in Battery mode.
The UPS is powering the equipment with battery
power. Prepare your equipment for shutdown.
Battery Low
LED is flashing slowly.
Continuous beep.
The UPS is in Battery mode and the
battery is running low.
This warning is approximate, and the actual
time to shutdown may vary significantly.
Depending on the UPS load and number of
Extended Battery Modules (EBMs), the Battery
Low warning may occur before the batteries
reach 25% capacity. See Table 13 on page 94
for estimated runtimes.
When utility power is restored, the UPS restarts
automatically, provides power to the load, and
charges the battery.
Battery Test
LED is flashing quickly.
1 long beep every 5 seconds.
A battery test is in progress.
Wait until the battery test completes.