SPECIFICATIONS
Eaton 9140 UPS (7.5–10 kVA) User's Guide
S
164201622 Rev 3
www.eaton.com/powerquality
94
Table 12. Battery
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
Type
Sealed, maintenance‐free, valve‐regulated, lead‐acid
Monitoring
Advanced monitoring for earlier failure detection and warning
Configuration
(32) 12V, 5 Ah
Charging (in minutes)
(10 kVA models)
266
336
368
398
419
Charging (in minutes)
(7.5 kVA models)
215
367
390
416
440
NOTE
Charging times are approximate and are to 80% usable capacity at nominal line voltage after full load discharge.
Table 13. Battery Runtimes (in Minutes)
Load
(10 kVA Models)
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
100% Load
5
12
27
35
45
75% Load
7
17
35
46
60
50% Load
12
27
52
69
90
25% Load
31
61
99
138
181
Load
(7.5 kVA Models)
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
100% Load
8.5
23.5
37.5
53
65.5
75% Load
12
30
52
69
86.5
50% Load
22
51.5
78.5
98.5
111
25% Load
48
94
116
>120
>180
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.