To locate the appropriate terminals on the HotSync CAN Bridge Card, see Figure
Figure 5-2. HotSync CAN Bridge Card connections
Table 5-1: HotSync CAN Bridge Card interface connections
1
J3
2
Connections for Parallel Systems Control
3
Connections for RPM II, RIM II, or SCM II
4
Connections for Bypass Status
5
Alarm
J3 Terminal
Name
Description
1
Alarm
Programmable UPS alarm. Activate by a remote dry contact closure.
2
Alarm Return
3
Alarm Relay NC
Normally-closed contact opens when UPS is on bypass.
4
Alarm Relay Com
Bypass contact return.
5
Alarm Relay NO
Normally-open contact closes when UPS is on bypass.
6
TX
RMP II, RIM II, and SCM II connections.
7
TX
8
CAN L
CAN interface for parallel operation.
9
CAN H
10
Shield
1
2
3
4
5
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide