130
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
7.6.6
Disable Variable Module Management System Mode from the UPS Command Menu
To disable Variable Module Management System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is
displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control
Command
screen is displayed.
4.
On the UPS Control Command screen, select
DISABLE VAR MODULE MANAGEMENT
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS transfers to Battery mode and then to Online mode in approximately ten seconds.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM
status
indicates ONLINE.
7.6.7
Start Variable Module Management System High Alert Mode from the UPS Command Menu
To start High Alert mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is
displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control
Command
screen is displayed.
4.
On the UPS Control Command screen, select
START HIGH ALERT
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS starts High Alert mode with the UPMs online supplying the critical load. After one
hour the UPS
transfers to Variable Module Management System mode.
The Online status indicator is illuminated. The UPS status indicates HIGH ALERT.
The UPM
status indicates ONLINE. The power module is on.
NOTE
•
•
The Variable Module Management System mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the Energy
Saver System mode is enabled, the Variable Module Management System mode commands will not be displayed.
NOTE
•
•
The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service
Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the Energy
Saver System mode is enabled, the Variable Module Management System mode commands will not be displayed.
Summary of Contents for Power Xpert 9395P 250 kVA
Page 1: ...User s and Installation Guide Power Xpert 9395P UPS 250 kVA 275 kVA 300 kVA...
Page 2: ......
Page 3: ...Power Xpert 9395P UPS 250 kVA 275 kVA 300 kVA User s and Installation Guide...
Page 168: ......
Page 169: ......
Page 170: ...614 01919 00...