134
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
7.6.14
Start Variable Module Management System High Alert Mode from
the Bypass
Command Menu
To start High Alert mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen
is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control
Command screen
is displayed.
4.
On the Bypass Control Command screen, select
START HIGH ALERT
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS starts High Alert mode with the UPMs online supplying
the critical load.
After one hour the UPS transfers to Variable Module Management
System mode.
The Online status indicator is illuminated. The UPS status indicates HIGH ALERT.
The UPM status
indicates ONLINE. The power module is on.
7.6.15
Starting the UPS UPMs
To start the power modules without transferring the critical load to Online mode:
1.
Unfasten the front door latches and swing the doors open on all of the UPSs (see Figure 4
‐
1).
2.
If the UPSs contain input breakers (CB1), verify that all input breakers are open.
3.
Close all UPS input feeder circuit breakers.
4.
Close all UPS Bypass input feeder circuit breakers.
5.
If the UPSs contain input breakers (CB1), close all input breakers.
6.
Close the doors and secure the latches.
7.
Observe the UPS control panel displays becoming active, indicating logic power.
8.
On any UPS, press the
CONTROLS
pushbutton on the main menu bar. The System Status
screen is
displayed.
9.
On the System Status screen, verify the UPS status is SHUTDOWN and the UPM status
is OFFLINE.
10.
Verify no alarms are active.
11.
On the System Status screen, select the
UPM
command. The UPS Control Command
screen is
displayed.
12.
On the UPS Control Command screen, select the
UPM 1
command.
13.
Press the
CONTROLS
pushbutton on the UPS Control Command menu bar. The UPM 1
Control
Command screen is displayed.
NOTE
•
•
The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service
Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the
Energy Saver System mode is enabled, the Variable Module Management System mode commands will not be
displayed.