118
Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
Table 8. Analog Screen Points (Continued)
Name
Units
Value
Index
Value Scale
Low Alarm
Index
High Alarm
Index
Output PF B
%
39
*100 (92=0.92)
199
570
Output PF C
%
40
*100 (92=0.92)
200
571
Total KW
KW
41
None
201
572
Xfers Total
Count
42
None
202
573
Xfers Since Car
Count
43
None
203
574
Out Volts THD A
%
44
68=68%
204
575
Out Volts A 3rd
%
45
68=68%
205
576
Out Volts A 5th
%
46
68=68%
206
577
Out Volts A 7th
%
47
68=68%
207
578
Out Volts A 9th
%
48
68=68%
208
579
Out Volts A 11th
%
49
68=68%
209
580
Out Volts A 13th
%
50
68=68%
210
581
Out Volts THD B
%
51
68=68%
211
582
Out Volts B 3rd
%
52
68=68%
212
583
Out Volts B 5th
%
53
68=68%
213
584
Out Volts B 7th
%
54
68=68%
214
585
Out Volts B 9th
%
55
68=68%
215
586
Out Volts B 11th
%
56
68=68%
216
587
Out Volts B 13th
%
57
68=68%
217
588
Out Volts THD C
%
58
68=68%
218
589
Out Volts C 3rd
%
59
68=68%
219
590
Out Volts C 5th
%
60
68=68%
220
591
Out Volts C 7th
%
61
68=68%
221
592
Out Volts C 9th
%
62
68=68%
222
593
Out Volts C 11th
%
63
68=68%
223
594
Out Volts C 13th
%
64
68=68%
224
595
Out Amps THD A
%
65
68=68%
225
596
Out Amps A 3rd
%
66
68=68%
226
597
Out Amps A 5th
%
67
68=68%
227
598
Out Amps A 7th
%
68
68=68%
228
599
Out Amps A 9th
%
69
68=68%
229
600