112
Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
Table 7. Digital Screen Points (Continued)
Name
Normal
Abnormal
Alarm
Alarm
Index
Status
Status
Index
Normal
Value
Open S1
OK
Alarm
Yes
22
No
1022
0
Open S2
OK
Alarm
Yes
23
No
1023
0
EPO
OK
Alarm
Yes
24
No
1024
0
Remote EPO
OK
Alarm
If Installed
25
No
1025
0
XFMR 1 HT
OK
Alarm
If Installed
26
If Installed
1026
0
XFMR 1 OT
OK
Alarm
If Installed
27
If Installed
1027
0
XFMR 2 HT
OK
Alarm
If Installed
28
If Installed
1028
0
XFMR 2 OT
OK
Alarm
If Installed
29
If Installed
1029
0
SCR High Temp
OK
Alarm
Yes
30
No
1030
0
SCR Over Temp
OK
Alarm
Yes
31
No
1031
0
Shunt Trip 1
OK
Trip
No
32
No
1032
0
Shunt Trip 2
OK
Trip
No
33
No
1033
0
DCPS S1V
OK
Alarm
Yes
34
No
1034
0
DCPS S2V
OK
Alarm
Yes
35
No
1035
0
DCPS OV
OK
Alarm
Yes
36
No
1036
0
S1 Rotation
OK
Alarm
Yes
37
No
1037
0
S2 Rotation
OK
Alarm
Yes
38
No
1038
0
On Source
Preferred
Alt
Yes
39
No
1039
0
Transfer
None
Done
No
40
No
1040
0
Shunt Trip
OK
Fail
No
41
No
1041
0
EPO Latched
OK
Alarm
No
42
No
1042
0
SAS D Open
OK
Alarm
Yes
43
No
1043
0
SAS D DC
OK
Alarm
Yes
44
No
1044
0
SAS D DC 1
OK
Alarm
Yes
45
No
1045
0
SAS D DC 2
OK
Alarm
Yes
46
No
1046
0
SAS D DC Main
OK
Alarm
Yes
47
No
1047
0
SAS D Pulse 1
OK
Alarm
Yes
48
No
1048
0
SAS D Pulse 2
OK
Alarm
Yes
49
No
1049
0
SAS D Pulse M
OK
Alarm
Yes
50
No
1050
0
SAS D Voting
OK
Alarm
Yes
51
No
1051
0
SAS D SCR 1 DC
Off
On
No
52
No
1052
0