Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
65
NOTE 1
The
SOURCE SELECTOR
switch operates slightly differently in Normal and Redundant
modes:
NOTE 2
In Normal mode, it sets the Preferred Source control to Source 1 or 2, as selected. This
can cause a transfer, if other circumstances allow it.
NOTE 3
In Redundant mode, it causes an immediate transfer to the specified source, if the
target power source is within specification and the load is not already on that source.
NOTE
The
MAINTENANCE
light on the ROI panel refers to the
Maintenance Bypass Switch
,
located next to the Contractor Board (see
). The Maintenance Bypass Switch is
used by service personnel to disable MCSW trip units during maintenance.