Figure 58. Load Screen
The
Load
Screen Bar Chart displays the current for both sources and the output, total KVA, peak KVA, and total
KW as bar charts. All bars start green, but turn yellow when they reach 80% or higher and turn red when they
reach 100% or higher.
Load values are defined by Eaton on the
Configuration
Screen (See
). 100% load values are stored in
the Analog Points list as Rated Total KVA (point 93) and Rated Phase Amp (point 94).
The
Trend
panel on the lower half of the screen shows the trend for total KVA.
1133..33..33 B
Brraanncchh S
Sccrreeeenn
The standalone TFA STS does not have distribution branch circuits and the Branch screen does not apply.
1133..44
H
Heellpp S
Sccrreeeenn
Touching the
Help
button on the
Home
screen displays
Help
screen, overlaid on the
Home
screen (see
paragraph
, and
The
Help
screen provides the operator a step-by-step procedure for going to and returning from Bypass. The
procedure steps are listed and tracked as operations are performed.
Touch the
Next
arrowhead to display another help procedure.