Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
1111..22
S
Sw
wiittcchh S
Seettttiinnggss S
Sccrreeeenn
Touch the
Switch
button in the navigation buttons to display the
Switch Settings
screen (see
). The
Switch Settings
screen is used to select or adjust parameters for sense and transfer algorithms.
Two of the three main transfer parameters—transfer algorithm and retransfer setting—are set on the Switch
Settings screen and require administrator or other higher-level authorization. The remaining choice—Preferred
Source
—is set on the
Home
screen and requires operator-level authorization.
Use the
Controls
panel to select the transfer algorithm and retransfer behavior by setting these virtual
switches:
•
Mode (VSS/POG)
: When the
VSS/POG
switch is touched to be moved, the
Execute
button is
highlighted as a precaution. The operator must touch
Execute
to move the virtual switch to the opposite
position, or
Cancel
to revert to the previous selection. (See paragraph
).
•
Retransfer (Yes/No)
: When
Retransfer=Yes
, the STS will switch back to the original preferred source
after an outage on that source has ended and the power on this source is within prescribed parameters.
When the
Retransfer
switch is touched to be moved,
Execute
is highlighted as a precaution. Touch
Execute to move the virtual switch to the opposite position, or
Cancel
to revert to the previous selection.
The remaining parameters are
Optimization parameters
for the sense, transfer, and retransfer algorithms.
These parameters have been experimentally set and optimized by Eaton.
NOTE:
Eaton strongly recommends
that the
Fast
,
Delayed
, and
Retransfer Delay
settings not be changed.
Figure 47. Switch Settings Screen