31
RACK MOUNTED FIXED SHELF
1. A Rack Mounted Fixed Shelf requires 1 U space. Using the numbers on the rails as a guide, locate the three
holes that define a U space at your desired shelf level. If your rails have a 3/8” square hole pattern, then snap
three #10-32 clip nuts onto each rack mount rail at the same U level. Clip nuts are not required on rails with
pre-threaded EIA holes. See figure
9-22
.
2. Assemble four shelf brackets to the shelf with #10 x 3/8” phillips pan head self tapping screws. Adjust the
position of the brackets to match the outside measurement of your rail spacing. See figure
9-23
.
3. Fasten the shelf to the rails using #10-32 x ½” phillips pan head machine screws. See figure
9-24
.
Figure
9-2
2
EIA hole pattern
Use this hole
Use this hole
Use this hole
Clip nuts
Rack mount rail
1-1/4”(1.25”)
Figure
9-2
4
Fixed shelf
Clip nuts
#10-32 x 5/8” Screw
w/nylon washer
Shelf bracket
Lock nuts
#10-24 x 3/8” phillips
pan head screws
Figure
9-2
3
Adjust brackets
as required
Fixed shelf
Pub Num: MN159002EN rev1.0