![background image](http://html1.mh-extra.com/html/eaton/mp-3000/mp-3000_manual_3823279021.webp)
I.L. 17562
Page 21
PR 0.3 Effective 8/99
Table 4.2 Monitor Mode Display
Page
Line
Complete Help Message
Description
MONITOR
MONITOR OF REAL TIME VALUES
Monitor mode
MONT I
REAL TIME DATA FROM CURRENT
MEASUREMENTS
Current monitoring data follows
IAVG XXX
AVERAGE OF THREE PHASE CURRENT
Average rms current of 3-phase
currents in amps
IA XXX
PHASE A CURRENT IN AMPS
Actual ac line motor rms current
IB XXX
PHASE B CURRENT IN AMPS
IC XXX
PHASE C CURRENT IN AMPS
IG XXX
GROUND FAULT CURRENT IN AMPS
Actual ground current
%IA XXX
PHASE A CURRENT AS A PERCENT OF FULL
LOAD AMPS
The percents of the actual
%IB XXX
PHASE B CURRENT AS A PERCENT OF FULL
LOAD AMPS
monitored current in amps
%IC XXX
PHASE C CURRENT AS A PERCENT OF FULL
LOAD AMPS
%UB XXX
PHASE UNBALANCE – IF POSITIVE THE RATIO
OF NEGATIVE TO POSITIVE SEQUENCE
CURRENT – IF NEGATIVE THE INVERSE
Ratio of negative sequence current to
positive sequence current in percent.
If a phase reversal exists, then the
ratio is inverted and a negative sign
is displayed.
MONT RTD
REAL TIME DATA FROM RTD MODULE
RTD monitoring data follows. Page
is only visible when an URTD is
communicating with the MP-3000
WT1 XXXX
WINDING TEMP 1 IN DEGREES F (or) C
RTD reading – terminals 1,2,3
WT2 XXXX
WINDING TEMP 2 IN DEGREES F (or) C
RTD reading – terminals 4,5,6
WT3 XXXX
WINDING TEMP 3 IN DEGREES F (or) C
RTD reading – terminals 7,8,9
WT4 XXXX
WINDING TEMP 4 IN DEGREES F (or) C
RTD reading – terminals 10,11,12
WT5 XXXX
WINDING TEMP 5 IN DEGREES F (or) C
RTD reading – terminals 13,14,15
WT6 XXXX
WINDING TEMP 6 IN DEGREES F (or) C
RTD reading – terminals 17,18,19
MT1 XXXX
MOTOR BEARING TEMP 1 IN DEGREES F (or)
C
RTD reading – terminals 20,21,22
MT2 XXXX
MOTOR BEARING TEMP 2 IN DEGREES F (or)
C
RTD reading – terminals 23,24,25
LT1 XXXX
LOAD BEARING TEMP 1 IN DEGREES F (or) C
RTD reading – terminals 26,27,28
LT2 XXXX
LOAD BEARING TEMP 2 IN DEGREES F (or) C
RTD reading – terminals 29,30,31
AXT XXXX
AUXILIARY TEMP IN DEGREES F (or) C
RTD reading – terminals 33,34,35
MONT MTR
REAL TIME MOTOR DATA
Motor monitoring data follows
VER XXXX
SOFTWARE VERSION NUMBER
MP-3000 software version in use
%I2T XXX
PERCENT OF I2T TRIP LEVEL
Percent of thermal bucket used
Summary of Contents for MP-3000
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...