Page 30
I.L. 17562
PR 0.3 Effective 8/99
Line
No.
Display
Help Message
Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
4
Choose:
GF A ON
GF T ON
Or
GF OFF
ENABLE GROUND FAULT
ALARM OR TRIP TO
ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between
GF A ON, GF T
ON, and GF OFF
GF OFF
5
Choose:
I2T A ON
I2T T ON
or
I2T OFF
ENABLE I2T ALARM OR TRIP
TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between
I2T A ON, I2T T
ON, and
I2T OFF
I2T T ON
6
Choose:
JAM A ON
JAM T ON
or
JAM OFF
ENABLE JAM ALARM OR
TRIP TO ACTIVATE AUX1
RELAY OUTPUT OR DISABLE
Toggles between
JAM A ON, JAM
T ON, and JAM
OFF
JAM OFF
7
Choose:
UL A ON
UL T ON
or
UL OFF
ENABLE UNDERLOAD ALARM
OR TRIP TO ACTIVATE AUX1
RELAY OUTPUT OR DISABLE
Toggles between
UL A ON, UL T
ON, and UL OFF
UL OFF
8
Choose:
UB A ON
UB T ON
or
UB OFF
ENABLE PHASE UNBALANCE
ALARM OR TRIP TO
ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between
UB A ON, UB T
ON, and UB OFF
UB OFF
9
Choose:
WD A ON
WD T ON
or
WD OFF
ENABLE WINDING TEMP
ALARM OR TRIP TO
ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between
WD A ON, WD
T ON, and WD
OFF
WD OFF
10
Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING
TEMP ALARM OR TRIP TO
ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between
MB A ON, MB T
ON, and
MB OFF
MB OFF
11
Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING
TEMP ALARM OR TRIP TO
ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between
LB A ON, LB T
ON, and LB OFF
LB OFF
12
Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD
TEMP ALARM OR TRIP TO
ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between
AX A ON, AX T
ON, and AX OFF
AX OFF
13
Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME
TRIP OR ALARM TO
ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between
SX A ON, SX T
ON, and SX OFF
SX OFF
14
Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN
STARTS TRIP TO ACTIVATE
AUX1 RELAY OUTPUT OR
DISABLE
Toggles between
TBS T ON, and
TBS OFF
TBS OFF
15
RTDF
ON
ENABLE RTD FAILURE
DIAGNOSTIC TO ACTIVATE
Toggles between
RTDF ON and
RTDF OFF
Summary of Contents for MP-3000
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...