Page 32
I.L. 17562
PR 0.3 Effective 8/99
Line
No.
Display
Help Message
Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
3
Choose:
I2T A ON
I2T T ON
Or
I2T OFF
ENABLE I2T ALARM OR TRIP
TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
I2T A ON, I2T T
ON, and
I2T OFF
I2T OFF
4
Choose:
JAM A ON
JAM T ON
Or
JAM OFF
ENABLE JAM ALARM OR
TRIP TO ACTIVATE AUX2
RELAY OUTPUT OR DISABLE
Toggles between
JAM A ON, JAM
T ON, and JAM
OFF
JAM OFF
5
Choose:
UL A ON
UL T ON
Or
UL OFF
ENABLE UNDERLOAD ALARM
OR TRIP TO ACTIVATE AUX2
RELAY OUTPUT OR DISABLE
Toggles between
UL A ON, UL T
ON, and UL OFF
UL OFF
6
Choose:
UB A ON
UB T ON
Or
UB OFF
ENABLE PHASE UNBALANCE
ALARM OR TRIP TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
UB A ON, UB T
ON, and UB OFF
UB OFF
7
Choose:
WD A ON
WD T ON
Or
WD OFF
ENABLE WINDING TEMP
ALARM OR TRIP TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
WD A ON, WD
T ON, and WD
OFF
WD OFF
8
Choose:
MB A ON
MB T ON
Or
MB OFF
ENABLE MOTOR BEARING
TEMP ALARM OR TRIP TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
MB A ON, MB T
ON, and
MB OFF
MB OFF
9
Choose:
LB A ON
LB T ON
Or
LB OFF
ENABLE LOAD BEARING
TEMP ALARM OR TRIP TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
LB A ON, LB T
ON, and LB OFF
LB OFF
10
Choose:
AX A ON
AX T ON
Or
AX OFF
ENABLE AUXILIARY RTD
TEMP ALARM OR TRIP TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
AX A ON, AX T
ON, and AX OFF
AX OFF
11
Choose:
SX A ON
SX T ON
Or
SX OFF
ENABLE STARTS PER TIME
TRIP OR ALARM TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
SX A ON, SX T
ON, and SX OFF
SX OFF
12
Choose:
TBS T ON
Or
TBS OFF
ENABLE TIME BETWEEN
STARTS TRIP OR TO
ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between
TBS T ON, and
TBS OFF
TBS OFF
13
RTDF
ON
Or
RTDF OFF
ENABLE RTD FAILURE
DIAGNOSTIC TO ACTIVATE
AUX2 RELAY OUTPUT OR
DISABLE
Toggles between
RTDF ON and
RTDF OFF
RTDF OFF
14
RTDF
ON
Or
RTDF OFF
ENABLE RTD FAILURE
DIAGNOSTIC TO ACTIVATE
AUX2 RELAY OUTPUT OR
DISABLE
Toggles between
RTDF ON and
RTDF OFF
RTDF OFF
Summary of Contents for MP-3000
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...