Capitole 40
1991.901 G01 002 37
Main current cables of outgoing feeder units in the fixed or
semi-withdrawable versions, are connected directly to the
equipment using cable lugs or terminals.
Attention: Outgoing main current cable connections on to
the horizontally positioned thermal relay should be made in
the order L1-L2-L3, from the bottom upwards
For outgoing feeders in the withdrawable version, the
cables are connected to the main connection-block via
recesses in the screening-plates.
This should be done as follows:
•
Remove the screening-plates by turning the quick
releases through 90°.
•
Release the terminal clamps on the main connection-
block by turning the hexagonal socket-head bolts to the
left, until they stop.
•
Tighten cables in acc. with torque indicated on main
connection -block
•
Wriggle cable to and for serveral times.
•
Re - tighten cable to the specified torque (see MBO
3034.552 B).
Figure 2-56: Cable connection to main connection -
block
•
Remove the auxiliary connection - block
(see Figure 3-28).
•
Connect the auxiliary current by plugging in the wires.
in the version with screws can then be tightened up. A
torque of 0.3 Nm may not be exceeded.
Figure 2-56a: Shaping of cable
In the version without screws the process should be
as follows:
•
A length of 8-9 mm insulation must be stripped
(Figure 2-57 ).
•
In order to keep the core together properly, the
insulation stripped off should not be removed before
being put into the clamp, but moved up slightly.
Figure 2-57: Stripped
Summary of Contents for Holec Capitole 40
Page 2: ...Administrative data Issue number G01 002 Date of issue 30 09 2008...
Page 62: ...Capitole 40 62 1991 901 G01 002 Place the draw out units into position Figure 3 35...
Page 74: ...Capitole 40 74 1991 901 G01 002 Figure 4 1...
Page 76: ...Capitole 40 76 1991 901 G01 002 Figure 4 2...
Page 78: ...Capitole 40 78 1991 901 G01 002 Figure 4 3...
Page 82: ...Capitole 40 82 1991 901 G01 002 Figure 4 5 Figure 4 6...
Page 84: ...Capitole 40 84 1991 901 G01 002 Figure 4 7...
Page 86: ...Capitole 40 86 1991 901 G01 002 Figure 4 8...
Page 88: ...Capitole 40 88 1991 901 G01 002 Figure 4 9...
Page 90: ...Capitole 40 90 1991 901 G01 002 Figure 4 10...
Page 92: ...Capitole 40 92 1991 901 G01 002 Figure 4 11...
Page 94: ...Capitole 40 94 1991 901 G01 002 Figure 4 12...
Page 96: ...Capitole 40 96 1991 901 G01 002 Figure 4 13...
Page 97: ...Capitole 40 1991 901 G01 002 97 APPENDIX 1 EU DECLARATION OF CONFORMITY...
Page 98: ...Capitole 40 98 1991 901 G01 002 APPENDIX 2 KEMA TEST REPORT...
Page 99: ...Capitole 40 1991 901 G01 002 99...
Page 100: ...Capitole 40 100 1991 901 G01 002 APPENDIX 3 LLOYD S CERTIFICATE...
Page 101: ...Capitole 40 1991 901 G01 002 101...