Removing a non-compartmented motor starter (max.
four starters in one compartment).
•
Open the door of the compartment concerned and the
cable compartment door.
•
Switch off all MCCBs (motor switches) and check that
the outgoing main power connections are isolated (live
components are IP20 protected).
•
Ensure that the MCCBs (motor switches) will not be
switched on in any way (the outgoing part of each
MCCB must remain isolated).
•
Remove the auxiliary power plugs from the terminal
strips that protrude into the cable compartment (also
remove the auxiliary power connections with the
auxiliary bars, if present).
•
Remove the outgoing main power cables and the
shielding plate in the cable compartment.
•
Remove the auxiliary cable bundle(s) from the door by
opening the bundle clips.
•
Push the interlock cams of the operating panel(s)
inwards and push the panel(s) out of the door, see
Figure 3-40.
•
Turn each panel and push it through the opening in the
door and back into the compartment. The auxiliary
cabling and the operating panel are now only
connected to the plug-in unit.
•
Loosen all the plug-in unit adapter captive fixing screws
(A) (mark the adapter position inside the compartment
to facilitate remounting).
•
Remove from the compartment the plug-in units
including the auxiliary cabling and the operating panel
that are still connected to it.
Figure 3-42
Fitting a non-compartmented motor starter (max.
four starters in one compartment)
Figure 3-43
•
Ensure that all MCCBs of the motor starters to be
connected are in the OFF position.
•
Place the plug-in unit(s) in the compartment and secure
it/them with the fixing bolts (use the markings that were
made previously, described in point 4.3.2.3).
•
Check that the outgoing main power circuits are
isolated.
A
Summary of Contents for Holec Capitole 40
Page 2: ...Administrative data Issue number G01 002 Date of issue 30 09 2008...
Page 62: ...Capitole 40 62 1991 901 G01 002 Place the draw out units into position Figure 3 35...
Page 74: ...Capitole 40 74 1991 901 G01 002 Figure 4 1...
Page 76: ...Capitole 40 76 1991 901 G01 002 Figure 4 2...
Page 78: ...Capitole 40 78 1991 901 G01 002 Figure 4 3...
Page 82: ...Capitole 40 82 1991 901 G01 002 Figure 4 5 Figure 4 6...
Page 84: ...Capitole 40 84 1991 901 G01 002 Figure 4 7...
Page 86: ...Capitole 40 86 1991 901 G01 002 Figure 4 8...
Page 88: ...Capitole 40 88 1991 901 G01 002 Figure 4 9...
Page 90: ...Capitole 40 90 1991 901 G01 002 Figure 4 10...
Page 92: ...Capitole 40 92 1991 901 G01 002 Figure 4 11...
Page 94: ...Capitole 40 94 1991 901 G01 002 Figure 4 12...
Page 96: ...Capitole 40 96 1991 901 G01 002 Figure 4 13...
Page 97: ...Capitole 40 1991 901 G01 002 97 APPENDIX 1 EU DECLARATION OF CONFORMITY...
Page 98: ...Capitole 40 98 1991 901 G01 002 APPENDIX 2 KEMA TEST REPORT...
Page 99: ...Capitole 40 1991 901 G01 002 99...
Page 100: ...Capitole 40 100 1991 901 G01 002 APPENDIX 3 LLOYD S CERTIFICATE...
Page 101: ...Capitole 40 1991 901 G01 002 101...