Capitole 40
34 1991.901 G01 002
With parallel, air-insulated busbars
Tee-off from the parallel horizontal busbar system to the
vertical busbars for outgoing feeders takes place by means
of a clamp-plate. A clamp-plate with two recesses is
mounted on the main busbars. This clamp-plate encloses
the main busbars and the tee-off bars are clamped using a
hexagonal socket-head bolt M12, see Figure 2-50.
The length of the clamping-bolt is the same as the bolt for
single busbar system tee-off, see table.
The connections of the tee-off strips tothe main busbars in
the case of feeder and bus couplers are made in the same
way as described above.
A serrated cupped washer is applied at the bottom of the
clamping-bolt.
A
TTENTION
Use the correct fixing bolts for these coupling.
Figure 2-49a: T- rails Plug – in
Figure 2-50: parallelle rails
Summary of Contents for Holec Capitole 40
Page 2: ...Administrative data Issue number G01 002 Date of issue 30 09 2008...
Page 62: ...Capitole 40 62 1991 901 G01 002 Place the draw out units into position Figure 3 35...
Page 74: ...Capitole 40 74 1991 901 G01 002 Figure 4 1...
Page 76: ...Capitole 40 76 1991 901 G01 002 Figure 4 2...
Page 78: ...Capitole 40 78 1991 901 G01 002 Figure 4 3...
Page 82: ...Capitole 40 82 1991 901 G01 002 Figure 4 5 Figure 4 6...
Page 84: ...Capitole 40 84 1991 901 G01 002 Figure 4 7...
Page 86: ...Capitole 40 86 1991 901 G01 002 Figure 4 8...
Page 88: ...Capitole 40 88 1991 901 G01 002 Figure 4 9...
Page 90: ...Capitole 40 90 1991 901 G01 002 Figure 4 10...
Page 92: ...Capitole 40 92 1991 901 G01 002 Figure 4 11...
Page 94: ...Capitole 40 94 1991 901 G01 002 Figure 4 12...
Page 96: ...Capitole 40 96 1991 901 G01 002 Figure 4 13...
Page 97: ...Capitole 40 1991 901 G01 002 97 APPENDIX 1 EU DECLARATION OF CONFORMITY...
Page 98: ...Capitole 40 98 1991 901 G01 002 APPENDIX 2 KEMA TEST REPORT...
Page 99: ...Capitole 40 1991 901 G01 002 99...
Page 100: ...Capitole 40 100 1991 901 G01 002 APPENDIX 3 LLOYD S CERTIFICATE...
Page 101: ...Capitole 40 1991 901 G01 002 101...