2. INSTRUCTIONS FOR
INSTALLATION
2.1 GENERAL
2.1.1 Transport and initial checking
TRANSPORT
Three different versions of sections may be supplied
depending upon the space available in the installation area,
namely:
•
Section of one cubicle, fitted with lifting-eyes for
transport. Lifting eyes may be used up to a maximum
weight per cubicle of 600 kgs. In the case of heavier
cubicles the auxiliary transport-frame supplied must be
used.
R
EMARK
When using lifting-eyes the protective cover of the
main busbar compartment should always be fitted.
•
Sections with a maximum of 1.5 m width. In order to
allow transport the units are provided with an angle
section on the top.
•
Sections with a width of a maximum of 3 m. For
transport purposes these cubicles are provided with an
angle section on the top and also a foundation frame.
These sections should be handled using a crane or a fork-
lift truck.
If the cubicles are to be temporarily stored, it is
recommended that they should not be unpacked. The
cubicles ought to be stored in a dry and preferable dust-
free area. Condensation as a result of rapid temperature
changes ought to be avoided.
Checking
After unpacking check the cubicles for any possible transit-
damage and/or whether any apparatus is missing. If the
cubicles have been damaged during transit, contact the
carrier and Eaton Holec in order to have the damage dealt
with.
Copper busbars, withdrawable circuit-breakers and fitting-
materials are always packed separately.
Figure 2-1: Transport of cubicles
Summary of Contents for Holec Capitole 40
Page 2: ...Administrative data Issue number G01 002 Date of issue 30 09 2008...
Page 62: ...Capitole 40 62 1991 901 G01 002 Place the draw out units into position Figure 3 35...
Page 74: ...Capitole 40 74 1991 901 G01 002 Figure 4 1...
Page 76: ...Capitole 40 76 1991 901 G01 002 Figure 4 2...
Page 78: ...Capitole 40 78 1991 901 G01 002 Figure 4 3...
Page 82: ...Capitole 40 82 1991 901 G01 002 Figure 4 5 Figure 4 6...
Page 84: ...Capitole 40 84 1991 901 G01 002 Figure 4 7...
Page 86: ...Capitole 40 86 1991 901 G01 002 Figure 4 8...
Page 88: ...Capitole 40 88 1991 901 G01 002 Figure 4 9...
Page 90: ...Capitole 40 90 1991 901 G01 002 Figure 4 10...
Page 92: ...Capitole 40 92 1991 901 G01 002 Figure 4 11...
Page 94: ...Capitole 40 94 1991 901 G01 002 Figure 4 12...
Page 96: ...Capitole 40 96 1991 901 G01 002 Figure 4 13...
Page 97: ...Capitole 40 1991 901 G01 002 97 APPENDIX 1 EU DECLARATION OF CONFORMITY...
Page 98: ...Capitole 40 98 1991 901 G01 002 APPENDIX 2 KEMA TEST REPORT...
Page 99: ...Capitole 40 1991 901 G01 002 99...
Page 100: ...Capitole 40 100 1991 901 G01 002 APPENDIX 3 LLOYD S CERTIFICATE...
Page 101: ...Capitole 40 1991 901 G01 002 101...