![Eaton Green Motion DC 44/66 Installation Manual Download Page 20](http://html1.mh-extra.com/html/eaton/green-motion-dc-44-66/green-motion-dc-44-66_installation-manual_3692091020.webp)
16
GREEN MOTION DC 44/66 EV CHARGER INSTALLATION MANUAL
MN192006EN March 2023 www.eaton.com
00 Title
Tag
Description
A
Top view of concrete base
B
Front view of concrete base
1
Hole for electrical cable
2
Concrete base
3
M10 stainless steel rod
5.2.2 Mounting the Green Motion DC 44/66 EV charger
When choosing the location of the EV charger, consider a 300 mm free space requirement to the left and right sides of
the EV charger for air circulation.
Fix the column using 4 x M10 stainless steel threaded rods on an 800 mm x 450 mm x 250 mm concrete base. The
power input electrical cable has to be fed through the concrete base through a hole with 48-mm diameter.
Below is a schematic representation of the concrete base of the EV charger column.
Figure 9. The top and front views of the concrete base of the EV charger with dimensions
800 mm (31.4 inch)
495 mm (19.5 inch)
180 mm (7.1 inch)
450 mm (17.7 inch)
250 mm (9.8 inch)
Ø 48 mm (1.9 inch)
Ø 10 mm (x4)
3
2
2
3
3
3
180
83 mm
(3.2 inch)
81 mm
(3.1 inch)
216 mm
(8.5 inch)
235 mm (9.2 inch)
A