34
User Manual
MN032006EN
Effective December 2017
415U Condor-long-range
wireless I/O and gateway
EATON
www.eaton.com
“Edit” Button:
This lets you edit the settings for the currently
selected table row. This activates the Edit
dialog box.
Name:
The item name displayed on the dashboard
display
Register:
This is the register that will be displayed on
the dashboard. Use the drop-down to select
from named registers, or use the
button
to display a full dialog to select any device
register.
Display Type:
Currently the “Text Value” option is only
supported. Future firmware releases may
support graphical display of analog values
Units:
(Analog registers only) Enter the text to display
for units.
Over/Under
Range Value:
(Analog registers only) If the displayed value
moves beyond these thresholds, the text
“Ovr” or “Und” is displayed instead of the
displayed value.
High / Low
Alarm:
If the displayed value moves beyond these
values, the dashboard item displays in red.
For Digital registers, set these both to 0 to
disable. Set High alarm to 1 to alarm with ON
state, and set Low alarm to 1 to alarm with
OFF state.
Invert:
For digital registers, use this to invert the
state, so that ON displays when the input is
off, and vice-versa.
Register/
Display Point 1/2:
For Analog registers, these four values set
the display scaling. You configure two points
which define what value will be displayed
as the register value changes. Refer to
section “Internal I/O” and “Analog Inputs” for
more detail on how the measured value is
represented in the registers.
Figure 55. Edit window