Modbus configuration
The 415U-2 provides Modbus TCP client/server and Modbus RTU
master/slave functionality for I/O transfer. Modbus TCP client,
Modbus RTU master, and Modbus TCP server/RTU slave can all be
supported simultaneously. When combined with the built-in Modbus
TCP-to-RTU converter, the 415U-2 can transfer I/O to and from
almost any combination of Modbus TCP or RTU devices.
The 415U-2 has predefined data areas for inputs and outputs and
the different I/O types (bits, words, long, floats, and so on), which
include the onboard input/outputs and are shared for both client and
server. For a full list of the available I/O and address locations see .
To change Modbus configuration parameters, click
Modbus
in
the project tree. The Modbus configuration screen (
Figure 58
) is
arranged in tabs. The main tabs are:
•
Modbus TCP Server and RTU Slave
—Used for configuring
Modbus TCP Server or RTU Slave parameters.
•
Modbus TCP Client and RTU Master
—Used for any Modbus
TCP Client and Modbus RTU Master Configuration parameters.
Figure 58. Modbus configuration
Modbus Master TCP
Client and RTU Master
Used to enable the Modbus master TCP client and RTU master. When this is disabled the screen appears as in
Figure 59
.
Scan Rate
Allows you to adjust the Modbus polling scan rate. The scan rate is the delay between the completion of one
request and the initiation of the next request.
Figure 59. Modbus master TCP client and RTU master disabled