January 2009
2.2.12 AI2 signal range
ID390
1
Signal range 0 – 20 mA
2
Signal range 4 – 20 mA
3
Signal range 0 – 10V
4
Signal range 2 – 10V
Note:
The selections have no effect if par. 2.2.13 > 0%, or par. 2.2.14 < 100%.
2.2.13
2.2.14
AI2 custom minimum
AI2 custom maximum
ID391
ID392
These parameters allow you to scale the input current signal between 0 and 20 mA.
Similar to parameters 2.2.7 and 2.2.8.
2.2.15 Analog input AI2 signal inversion
ID398
See corresponding parameter 2.2.9.
2.2.16 Analog input AI2 signal filter time
ID389
See corresponding parameter 2.2.10.
2.2.17 Motor potentiometer memory reset
(Frequency reference)
ID367
0
No reset
1
Memory reset in stop and powerdown
2
Memory reset in powerdown