SLX9000 Adjustable Frequency Drives User Manual
8-8
For more information visit:
www.eaton.com
MN04003020E
January 2009
Table 8-5: Basic Parameters P2.1, continued
Code
Parameter
Min.
Max.
Unit
Default
Cust
ID
Note
P2.1.16
Analog output
function
0
12
1
307
0
= Not used
1
= Output freq. (0 – f
max
)
2
= Freq. reference (0 – f
max
)
3
= Motor speed (0 – Motor nominal
speed)
4
= Output current (0 – I
nMotor
)
5
= Motor torque (0 – T
nMotor
)
6
= Motor power (0 – P
nMotor
)
7
= Mot. voltage (0 – V
nMotor
)
8
= DC-link volt (0 – 1000V)
9
= PI controller ref. value
10
= PI contr. act. value 1
11
= PI contr. error value
12
= PI controller output
P2.1.17
DIN2 function
0
10
1
319
0
= Not used
1
= Start Reverse (DIN1 = Start
forward)
2
= Reverse (DIN1 = Start)
3
= Stop pulse (DIN1 = Start pulse)
4
= External fault, cc
5
= External fault, oc
6
= Run enable
7
= Preset speed 2
8
= Motor pot. UP (cc)
9
= Disable PID (Direct freq.
reference)
10
= Interlock 1
P2.1.18
DIN3 function
0
17
6
301
0
= Not used
1
= Reverse
2
= External fault, cc
3
= External fault, oc
4
= Fault reset
5
= Run enable
6
= Preset speed 1
7
= Preset speed 2
8
= DC-braking command
9
= Motor pot. UP (cc)
10
= Motor pot. DOWN (cc)
11
= Disable PID (Direct freq.
reference)
12
= PID Keypad ref. 2 selection
13
= Interlock 2
14
= Thermistor input
Note! See
Page 4-9
15
= Force control place to I/O
16
= Force control place to Fieldbus
17
= AI1/AI2 selection for I/O
reference
Summary of Contents for Cutler-Hammer SLX9000 Series