Table 7-2: Basic Parameters (Control Keypad: Menu P2
➔
B2.1) (Continued)
Code
Parameter
Min.
Max.
Unit
Default
Cust.
ID
Note
P2.1.16 Analog output
function
0
12
1
307
0
= Not used
1
= Output freq. (0 – f
max
)
2
= Freq. reference (0 – f
max
)
3
= Motor speed (0 – Motor
nominal speed)
4
= Output current (0 – I
nMotor
)
5
= Motor torque (0 – T
nMotor
)
6
= Motor power (0 – P
nMotor
)
7
= Motor voltage (0 – U
nMotor
)
8
= DC-link volt (0 – U
nMotor
)
9
= PI controller ref. value
10
= PI contr. act. value 1
11
= PI contr. error value
12
= PI controller output
P2.1.17
DIN2 function
0
10
1
319
0
= Not used
1
= Start Reverse
2
= Reverse
3
= Stop pulse
4
= External fault, cc
5
= External fault, oc
6
= Run enable
7
= Preset speed 2
8
= Motor pot. UP (cc)
9
= Disable PID (Direct freq.
reference)
10
= Interlock 1
P2.1.18
DIN3 function
0
16
6
301
0
= Not used
1
= Reverse
2
= External fault, cc
3
= External fault, oc
4
= Fault reset
5
= Run enable
6
= Preset speed 1
7
= Preset speed 2
8
= DC-braking command
9
= Motor pot. UP (cc)
10
= Motor pot. DOWN (cc)
11
= Disable PID (PID control
selection)
12
= PID Keypad ref. 2
selection
13
= Interlock 2
14
= Thermistor input (See
Page 4-9
)
15
= Force CP to I/O
16
= Force CP to Fieldbus
P2.1.19 Preset speed 1
0.00
Par. 2.1.2
Hz
10.00
105
P2.1.20 Preset speed 2
0.00
Par. 2.1.2
Hz
50.00
106
P2.1.21 Automatic restart
0
1
0
731
0
= Not used
1
= Used
P2.1.22 Parameter conceal
0
1
1
115
0
= All parameters and menus
visible
1
= Only group P2.1 and
menus M1 – H5 visible