Output Signals (Control Keypad: Menu P2
➔
P2.3)
Table 8-7: Output Signals, G2.3
Code
Parameter
Min.
Max.
Unit
Default
Cust
ID
Note
P2.3.1
Relay output 1
function
0
20
3
313
0
= Not used
1
= Ready
2
= Run
3
= Fault
4
= Fault inverted
5
= FC overheat warning
6
= Ext. fault or warning
7
= Ref. fault or warning
8
= Warning
9
= Reversed
10
= Preset speed
11
= At speed
12
= Mot. regulator active
13
= OP freq. limit superv.1
14
= Control place: IO
15
= Thermistor fault/ warning
16
= Actual value supervision
17
= Autochange 1 control
18
= Autochange 2 control
19
= Autochange 3 control
20
= AI supervision
P2.3.2
Expander board
relay output 1
function
0
19
2
314
Same as parameter 2.3.1
P2.3.3
Expander board
relay output 2
function
0
19
3
317
Same as parameter 2.3.1
P2.3.4
Expander board
digital output 1
function
0
19
1
312
Same as parameter 2.3.1
P2.3.5
Analog output
function
0
12
1
307
See parameter 2.1.16
P2.3.6
Analog output
filter time
0.00
10.00
s
1.00
308
0
= No filtering
P2.3.7
Analog output
inversion
0
1
0
309
0
= Not inverted
1
= Inverted
P2.3.8
Analog output
minimum
0
1
0
310
0
= 0 mA
1
= 4 mA
P2.3.9
Analog output
scale
10
1000
%
100
311
P2.3.10
Expander board
analog output 1
function
0
12
0
472
Same as parameter 2.1.16
P2.3.11
Expander board
analog output 2
function
0
12
0
479
Same as parameter 2.1.16
P2.3.12
Output frequency
limit 1
supervision
0
2
0
315
0
= No limit
1
= Low limit supervision
2
= High limit supervision
P2.3.13
Output frequency
limit 1;
Supervised value
0.00
Par.
2.1.2
Hz
0.00
316