SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit:
www.eaton.com
8-13
January 2009
Motor Control Parameters (Control Keypad: Menu P2
➔
P2.6)
Table 8-10: Motor Control Parameters, P2.6
Protections (Control Keypad: Menu P2
➔
P2.7)
Table 8-11: Protections, P2.7
Code
Parameter
Min.
Max.
Unit
Default
Cust
ID
Note
P2.6.1
Motor control
mode
0
1
0
600
0
= Frequency control
1
= Speed control
P2.6.2
VHz ratio selection 0
3
0
108
0
= Linear
1
= Squared
2
= Programmable
3
= Linear with flux optim.
P2.6.3
Field weakening
point
30.00
320.00
Hz
50.00
602
P2.6.4
Voltage at field
weakening point
10.00
200.00
%
100.00
603
n% x U
nmot
P2.6.5
VHz curve
midpoint
frequency
0.00
par.
P2.6.3
Hz
50.00
604
P2.6.6
VHz curve
midpoint voltage
0.00
100.00
%
100.00
605
n% x U
nmot
Parameter max. value = par. 2.6.4
P2.6.7
Output voltage at
zero frequency
0.00
40.00
%
0.00
606
n% x U
nmot
P2.6.8
Switching
frequency
1.0
16.0
kHz
6.0
601
Depends on hp
P2.6.9
Overvoltage
controller
0
1
1
607
0
= Not used
1
= Used
P2.6.10
Undervoltage
controller
0
1
1
608
0
= Not used
1
= Used
P2.6.11
Identification
0
1
0
631
0
= No action
1
= ID no run
Code
Parameter
Min.
Max.
Unit
Default
Cust
ID
Note
P2.7.1
Response to 4 mA
reference fault
0
3
0
700
0
= No response
1
= Warning
2
= Fault, stop acc. to 2.1.12
3
= Fault, stop by coasting
P2.7.2
Response to
external fault
0
3
2
701
0
= No response
1
= Warning
2
= Fault, stop acc. to 2.1.12
3
= Fault, stop by coasting
P2.7.3
Response to
undervoltage fault
1
3
2
727
P2.7.4
Output phase
supervision
0
3
2
702
P2.7.5
Ground fault
protection
0
3
2
703
P2.7.6
Thermal
protection of the
motor
0
3
2
704
P2.7.7
Motor ambient
temperature factor
-100.0
100.0
%
0.0
705