SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit:
www.eaton.com
8-9
January 2009
Table 8-5: Basic Parameters P2.1, continued
Input Signals (Control Keypad: Menu P2
➔
P2.2)
Table 8-6: Input Signals, P2.2
Code
Parameter
Min.
Max.
Unit
Default
Cust
ID
Note
P2.1.19
Preset speed 1
0.00
Par.
2.1.2
Hz
10.00
105
P2.1.20
Preset speed 2
0.00
Par.
2.1.2
Hz
50.00
106
P2.1.21
Automatic restart
0
1
0
731
0
= Not used
1
= Used
P2.1.22
Parameter conceal
0
1
0
115
0
= All parameters and menus
visible
1
= Only group P2.1 and menus M1
to H5 visible
Code
Parameter
Min.
Max.
Unit
Default
Cust
ID
Note
P2.2.1
Expander board
DIE1 function
0
13
7
368
0
= Not used
1
= Reverse
2
= External fault, cc
3
= External fault, oc
4
= Fault reset
5
= Run enable
6
= Preset speed 1
7
= Preset speed 2
8
= DC-braking command
9
= Motor pot. UP (cc)
10
= Motor pot. DOWN (cc)
11
= Disable PID (PID control
selection)
12
= PID Keypad ref. 2 selection
13
= Interlock 1
P2.2.2
Expander board
DIE2 function
0
13
4
330
Same as parameter 2.2.1, except:
13
= Interlock 2
P2.2.3
Expander board
DIE3 function
0
13
11
369
Same as parameter 2.2.1, except:
13
= Interlock 3
P2.2.4
DIN4 function (AI1)
0
13
2
499
Used if P2.2.6 = 0
Selections same as in parameter 2.2.3
P2.2.5
AI1 signal selection 0
10
377
10
= AI1 (
1
= Local,
0
= input 1)
11
= AI2 (
1
= Local,
1
= input 2)
20
= Exp. AI1 (
2
= exp. board,
0
=
input 1)
21
= Exp AI2 (
2
= exp. board,
1
=
input 2)
P2.2.6
AI1 signal range
1
4
3
379
0
= Digital input 4
1
= 0 – 20 mA
2
= 4 – 20 mA
3
= 0 – 10V
4
= 2 – 10V
Not used if AI2 Custom min > 0% or
AI2 custom max. < 100%
Note!
See
Page 5-22
Summary of Contents for Cutler-Hammer SLX9000 Series
Page 1: ...SLX9000 Adjustable Frequency Drives User Manual Effective January 2009 Supersedes October 2008...
Page 2: ......
Page 171: ......