SLX9000 Adjustable Frequency Drives User Manual
5-26
For more information visit:
www.eaton.com
MN04003020E
January 2009
Slave Address (P6.10.3)
Sets the slave address for the Modbus protocol. You can set any address between 1 and 255.
Baud Rate (P6.10.4)
Selects the baud rate used with the Modbus communication.
0
= 300 baud
1
= 600 baud
2
= 1200 baud
3
= 2400 baud
4
= 4800 baud
5
= 9600 baud
6
= 19200 baud
7
= 38400 baud
8
= 57600 baud
Stop Bits (P6.10.5)
Sets number of stop bits used in Modbus communication.
0
= 1 stop bit
1
= 2 stop bits
Parity Type (P6.10.6)
Here you can select the type of parity checking used with the Modbus communication.
0
= None
1
= Odd
2
= Even
Communication time-out (P6.10.7)
If communication between two messages is broken for a longer time than that defined by this
parameter, a communication error is initiated. If the value of this parameter is
0
, the function
is not used.
0
= Not used
1
= 1 second
2
= 2 seconds, etc.
Expander Board Menu (E7)
The
Expander board menu
makes it possible for the user 1) to see which expander board is
connected to the control board and 2) to reach and edit the parameters associated with the
expander board.
Enter the following menu level (
E#
) with the Menu Button Right. You can view and edit the
parameter values in the same way as described on
Page 5-8
.
Further Keypad Functions
The SLX9000 control keypad embodies additional application-related functions. See Eaton’s
Multi-Control Application Manual
for more information.