18
4. Construction and Function
MANUAL CEAG AUtoMAtiC tEst systEM At-s
+
40071860177 (C) December 2016 www.ceag.de
SU S+ 2 x 6 A with STAR
+
Technology
Number of circuits
2
Rated current per circuit
6 A
Fuse protection per circuit
10 AT
Max. inrush peak current
250 A
Max. cable diameter circuit outlets
flexible 2.5 mm² with wire end sleeve
and rigid 4 mm²
Max. cable diameter feed
flexible 4 mm² with wire end sleeve
and rigid 6 mm²
Weight
350 g
H x W X D (in mm)
107 x 90 x 58
Module width
6 subunits
Item no.
400 71 360 350
SOU S+ 2 x 4 A with rental current feed and
STAR
+
Technology
Number of circuits
2
Rated current per circuit
4 A
Fuse protection per circuit
8 AT
Max. inrush peak current
250 A per circuit
Max. cable diameter
flexible 2.5 mm² with wire end sleeve
and rigid 4 mm²
Weight
625 g
H x W X D (in mm)
178 x 108 x 60
Module width
10 subunits
Item no.
400 71 360 461
4.4.3 Circuit change-over modules overview (SU/SOU)