7
3. Technical Data
MANUAL CEAG AUtoMAtiC tEst systEM At-s
+
40071860177 (C) December 2016 www.ceag.de
3.2 Data Sheet for AT-S
+
C16
Type of system
AT-S
+
C16
Construction
Sheet steel cabinet with partial
viewing window in the door
Height
1800 mm
Width
600 mm
Depth
400 mm
Weight
approx. 120 kg
Insulation class
I
Degree of protection
IP 21
External painting
Structure powder laquer RAL 7035
light grey
Cable entry
at the top (prepunched roof sheeting)
at the bottom (open bottom with
propping tracks on the side)
Hinge
right
Mains rated voltage
400V AC, 50/60 Hz
Ambient temperature operation (please
attend to the attachted operating and
installation instructions)
-5°C up to +35°C
Mains feed in (max. 50 mm²)
Q1
Max. 60 circuits (max. 4 mm²)*
X1.1, X2.1, X3.1, X4.1
Marshalling mains (max. 16 mm²)
F10 - F15
Addresses optional places DLS-3Ph, TLS
(max. 2.5 mm²)
customised
Connection to ext. control switch
(max. 4 mm²)
X1.1.S1-S2
Connection to 24V current loop
(max. 4 mm²)
X1.1.S3-S4
Connection to potential-free signal
contacts (max. 4 mm²)
X1.1.C0 14; 12; 24; 22; 34; 32/C1
44; 54
Connection to CG-S Bus (max. 4 mm²)
X1.1.A-B
Connection to RS485 Bus (max. 4 mm²)
X1.1.RS485.A-B
Connection to 24V analog output
(max. 4 mm²)
X1.1.+24V Out--24V Out
Connection to 24V analog input
(max. 4 mm²)
X1.1.Z1.1-Z1.2/Z2.1-Z2.2/Z3.1-Z3.2/
Z4.1-Z4.2
* Max. 2.5mm² flexible with wiring sleeve. The final circuits get wired customised.
600
400
600
400
1800
Interior side view, left
Interior side view, right
Front view, open
600
400
600
400
1800